Enhanced boiling of HFE-7100 dielectric liquid on porous graphite

被引:87
作者
El-Genk, MS [1 ]
Parker, JL [1 ]
机构
[1] Univ New Mexico, Inst Space & Nucl Power Studies, Dept Chem & Nucl Engn, Albuquerque, NM 87131 USA
关键词
pool boiling; HFE-7100 dielectric liquid; immersion cooling; porous graphite; subcooling; temperature excursion;
D O I
10.1016/j.enconman.2004.11.012
中图分类号
O414.1 [热力学];
学科分类号
摘要
Enhanced boiling of HFE-7100 dielectric liquid on porous graphite measuring 10 mm x 10 mm is investigated, and results are compared with those for smooth copper (Cu) of the same dimensions. Although liquid is out-gasscd for hours before performing the pool boiling experiments, air entrapped in re-entrant type cavities, ranging in size from tens to hundreds of microns, not only enhanced the nucleate boiling heat transfer and the critical heat flux (CHF), but also, the mixing by the released tiny air bubbles from the porous graphite prior to boiling incipience enhanced the natural convection heat transfer by similar to 19%. No temperature excursion is associated with the nucleate boiling on porous graphite, which ensues at very low surface superheat of 0.5-0.8 K. Conversely, the temperature overshoot at incipient boiling on Cu is as much as 39.2, 36.6, 34.1 and 32.8 K in 0 (saturation), 10, 20 and 30 K subcooled boiling, respectively. Nucleate boiling ensues on Cu at a surface superheat of 11.9, 10.9, 9.5 and 7.5 K in 0 (saturation), 10, 20 and 30 K subcooled boiling, respectively. The saturation nucleate boiling heat flux on porous graphite is 1700% higher than that on Cu at a surface superheat of similar to 10 K and decreases exponentially with increased superheat to similar to 60% higher near CHF. The CHF values of HFE-7100 on porous graphite of 31.8, 45.1, 55.9 and 66.4 W/cm(2) in 0 (saturation), 10, 20 and 30 K subcooled boiling, are 60% higher and the corresponding superheats are 25% lower than those on Cu. In addition, the rate of increase in CHF with increased liquid subcooling is 50% higher than that on Cu. (c) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2455 / 2481
页数:27
相关论文
共 47 条
[1]  
*3M, 2001, TECHN DAT SHEETS PRO
[2]  
ARBELAEZ F, 2000, P 34 NAT HEAT T C, V1, P759
[3]  
ARIK M, 2001, P PAC RIM INT EL PAK
[4]  
ARVELO A, 2004, P 9 INT C THERM PHEN, V2, P23
[5]   Towards optimizing enhanced surfaces for passive immersion cooled heat sinks [J].
Baldwin, CS ;
Bhavnani, SH ;
Jaeger, RC .
ITHERM '98: SIXTH INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS, 1998, :399-408
[6]   Enhanced boiling heat transfer from micro-porous cylindrical surfaces in saturated FC-87 and R-123 [J].
Chang, JY ;
You, SM .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1997, 119 (02) :319-325
[7]  
CHANG JY, 1996, ASME, V118, P937
[8]  
CHEN XY, 2004, P 9 INT C THERM PHEN, V1, P199
[9]   Pool boiling in saturated and subcooled HFE-7100 dielectric fluid from a porous graphite surface [J].
El-Genk, MS ;
Parker, JL .
ITHERM 2004, VOL 1, 2004, :655-662
[10]   Combined effects of subcooling and surface orientation on pool boiling of HFE-7100 from a simulated electronic chip [J].
El-Genk, MS ;
Bostanci, H .
EXPERIMENTAL HEAT TRANSFER, 2003, 16 (04) :281-301