Comprehensive Assessment of Lightning Protection Schemes for 10 kV Overhead Distribution Lines

被引:20
|
作者
Cao, Jinxin [1 ]
Du, Yaping [1 ]
Ding, Yuxuan [1 ]
Qi, Ruihan [2 ]
Li, Binghao [1 ]
Chen, Mingli [1 ]
Li, Zhe [3 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hung Hom, Hong Kong, Peoples R China
[2] China Southern Power Grid, State Key Lab HVDC Transmiss Technol, Guangzhou 510000, Peoples R China
[3] China Southern Power Grid, Shenzhen Power Supply Bur, Shenzhen 10000, Peoples R China
关键词
Lightning; Wires; Surges; Arresters; Lightning protection; Monte Carlo methods; Flashover; overhead line; Monte Carlo simulation; medium voltage; economic analysis; POWER DISTRIBUTION LINES; INDUCED VOLTAGES; INDUCED OVERVOLTAGES; SHIELD WIRES; PERFORMANCE; ARRESTERS; SYSTEMS;
D O I
10.1109/TPWRD.2021.3110248
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents an assessment of lightning protection schemes for overhead lines from two aspects: protection performance and economic cost. Considering the random nature of lightning, the Monte-Carlo method with a heuristic technique is applied in the assessment. The one-dimensional finite-difference time-domain method is adopted to evaluate lightning overvoltages on insulators and lightning currents in surge arresters for failure assessment. The failure rate of an overhead line is addressed under both direct lightning and indirect lightning. A reduced set of design parameters are identified. It is found that the line insulation itself with a critical flashover overvoltage of less than 200 kV is not sufficient for lightning protection, especially against direct strokes. With other protection options, however, increasing the insulation level can greatly improve the protection performance. Installing surge arresters on every pole results in the best protection performance, but could be extremely expensive due to the replacement of failed surge arresters. The shielding wire provides moderate protection performance with a relatively low cost. The combination of the shielding wire and surge arresters provides much better performance under a wide range of soil conductivity with a moderate cost. It is worth mentioning that adopting high insulation strength for overhead lines in the new-line design could lead to significant cost savings for lightning protection. Guidelines for selecting design parameter values and protection schemes are provided, as well as a procedure for performance-cost evaluation.
引用
收藏
页码:2326 / 2336
页数:11
相关论文
共 50 条
  • [1] Research on comprehensive protections of 10 kV overhead insulated distribution lines from lightning
    Henan Luohe Electric Power Company, Luohe 462001, China
    不详
    Gaodianya Jishu, 2008, 11 (2395-2399):
  • [2] Practical Schemes on Lightning Energy Suppression in Arresters for Transformers on 10 kV Overhead Distribution Lines
    Cao, Jinxin
    Du, Yaping
    Ding, Yuxuan
    Qi, Ruihan
    Li, Binghao
    Chen, Mingli
    Li, Zhe
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (05) : 4272 - 4281
  • [3] Research on Lightning Overvoltage and Comprehensive lightning proof measures of 10kV Overhead Insulated Distribution Lines
    Han Xuemin
    Mao Minghua
    Wu Jianbin
    Zhou Wenjun
    Yu Jianhui
    Tu jun
    Wang Xiaofeng
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 4035 - +
  • [4] Simulation of Lightning Protection Effect for Overhead Ground Wire of 10kV Distribution Lines
    Zhang, Haiquan
    Li, Xianqiang
    Wei, Chen
    Ma, Zhiyuan
    Mao, Kedan
    Wu, Xixiu
    2019 4TH INTERNATIONAL CONFERENCE ON INTELLIGENT GREEN BUILDING AND SMART GRID (IGBSG 2019), 2019, : 270 - 273
  • [5] Indirect lightning performance of 10-kV overhead distribution lines
    Yu, Jianli
    Gu, Shanmao
    Liu, Jianjun
    Liu, He
    FRONTIERS IN ENERGY RESEARCH, 2024, 12
  • [6] Lightning protection of overhead power distribution lines
    Yokoyama, Shigeru
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2007, 2 (05) : 491 - 496
  • [7] Research on lightning protection of overhead power distribution lines
    Yokoyama, Shigeru
    Sato, Tomoyuki
    Gaodianya Jishu/High Voltage Engineering, 2013, 39 (10): : 2317 - 2328
  • [8] Lightning protection of MEA's 24 kV distribution lines Using overhead ground wires
    Sestasombut, P.
    Ngaopitakkul, A.
    2017 IEEE INNOVATIVE SMART GRID TECHNOLOGIES - ASIA (ISGT-ASIA), 2017, : 793 - 797
  • [9] Waveform Analysis on Characteristics of Lightning Induced Overvoltages on 10kV Overhead Distribution Lines
    Yang Q.
    Zhang X.
    Sun J.
    Xu W.
    He W.
    Wang K.
    Qin Z.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2022, 42 (24): : 8900 - 8909
  • [10] Performance Against Direct Lightning on 10-kV Overhead Distribution Lines With Counterpoise Wires
    Cao, Jinxin
    Du, Yaping
    Ding, Yuxuan
    Li, Zhe
    Chen, Mingli
    Qi, Ruihan
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2023, 65 (04) : 1108 - 1116