Experimental and numerical simulation studies on diesel pool fire

被引:13
作者
Sahu, Deepak [1 ]
Kumar, Shashi [1 ]
Jain, Shorab [2 ]
Gupta, Akhilesh [3 ]
机构
[1] Indian Inst Technol Roorkee, Dept Chem Engn, Roorkee 247667, Uttar Pradesh, India
[2] CSIR Cent Bldg Res Inst Roorkee, Fire Res Div, Roorkee 247667, Uttar Pradesh, India
[3] Indian Inst Technol Roorkee, Dept Mech & Ind Engn, Roorkee 247667, Uttar Pradesh, India
关键词
compartment fire; diesel pool fire; temperature; heat flux; CFD modeling; LARGE-EDDY SIMULATION; COMPARTMENT FIRE;
D O I
10.1002/fam.2361
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Experimental studies are performed under different ventilation conditions to investigate the effect of ventilation on compartment fires. A compartment of size 4mx4mx4m having a door of size 2mx1m is used for experiments. The experiments are conducted with full door open and half door open conditions. Diesel, used as a fuel source, is placed in a pan of 40cm diameter and 15cm height, which is kept in the center of the compartment. During experiments a constant 12cm height of the fuel is maintained above the pan bottom. The maximum heat release rate is found to be 100kW and 115kW in full door open and half door open experiments respectively. It is observed that the size of door opening affected the heat release rate, burning rate and thermal environment inside the compartment after the growth period of 800s. The numerical simulation is also performed for full door open experiment using CFD code, Fire Dynamics Simulator (FDS, version 6.0.1) developed by NIST. Simulation is accomplished with the refinement of mesh size near the fire source; results from FDS closely match with the experimental results. Copyright (c) 2016 John Wiley & Sons, Ltd.
引用
收藏
页码:1016 / 1035
页数:20
相关论文
共 36 条
[1]  
Aljumaiah O., 2014, Fire Saf. Sci., P331, DOI [10.3801/IAFSS.FSS.11-331, DOI 10.3801/IAFSS.FSS.11-331]
[2]   An overview of design fires for building compartments [J].
Bwalya, Alex .
FIRE TECHNOLOGY, 2008, 44 (02) :167-184
[3]   Numerical Studies on Heat Release Rate in Room Fire on Liquid Fuel under Different Ventilation Factors [J].
Cai, N. ;
Chow, W. K. .
INTERNATIONAL JOURNAL OF CHEMICAL ENGINEERING, 2012, 2012
[4]  
Chow W. K., 2003, Archit. Sci. Rev, V46, P291, DOI [10.1080/00038628.2003.9696996, DOI 10.1080/00038628.2003.9696996]
[5]  
Chow W. K., 1993, FIRE SCI TECHNOLOGY, V13, P71
[6]   Correlation equations on fire-induced air flow rates through doorway derived by large eddy simulation [J].
Chow, WK ;
Zou, GW .
BUILDING AND ENVIRONMENT, 2005, 40 (07) :897-906
[7]   THE CHALLENGE OF FIRE MODELING [J].
COX, G .
FIRE SAFETY JOURNAL, 1994, 23 (02) :123-132
[8]   Compartment fire near-field entrainment measurements [J].
Dembsey, NA ;
Pagni, PJ ;
Williamson, RB .
FIRE SAFETY JOURNAL, 1995, 24 (04) :383-419
[9]  
DiNenno PJ, 2002, SFPE HDB FIRE PROTEC, P297
[10]  
Gottuk DT, 1997, FIR SAF SCI P 5 INT, V5, P935