CT Saturation Detection Based on Waveform Analysis Using a Variable-Length Window

被引:34
作者
Hooshyar, Ali [1 ]
Sanaye-Pasand, Majid [1 ]
机构
[1] Univ Tehran, Control & Intelligent Proc Ctr Excellence, Sch Elect & Comp Engn, Coll Engn, Tehran 14395515, Iran
关键词
Current transformer; fault current; least-error-squares technique; saturation detection; CURRENT TRANSFORMERS; DETECTION ALGORITHM; COMPENSATION; PROTECTION; SERIES;
D O I
10.1109/TPWRD.2011.2142404
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Saturation of current transformers (CTs) can lead to maloperation of protective relays. Using the waveshape differences between the distorted and undistorted sections of fault current, this paper introduces a novel method to quickly detect CT saturation. First, a symmetrical variable-length window is defined for the current waveform. The least error squares technique is employed to process the current inside this window and make two estimations for the current samples exactly before and after the window. CT saturation can be identified based on the difference between these two estimations. The accurate performance of this method is independent of the CT parameters, such as CT remanence and its magnetization curve. Moreover, the proposed method is not influenced by the fault current characteristics, noise, etc., since it is based on the significant differences between the distorted and undistorted fault currents. Extensive simulation studies were performed using PSCAD/EMTDC software and the fast and reliable response of the proposed method for various conditions, including very fast and mild saturation events, was demonstrated.
引用
收藏
页码:2040 / 2050
页数:11
相关论文
共 29 条
[1]  
*ABB, APPL MAN REB500 REB5
[2]   A current transformer model based on the Jiles-Atherton theory of ferromagnetic hysteresis [J].
Annakkage, UD ;
McLaren, PG ;
Dirks, E ;
Jayasinghe, RP ;
Parker, AD .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (01) :57-61
[3]  
[Anonymous], 2009, C37234 IEEE
[4]  
[Anonymous], 2007, C37235 IEEE
[5]   Fast and Reliable CT Saturation Detection Using a Combined Method [J].
Dashti, Hamed ;
Pasand, Majid Sanaye ;
Davarpanah, Mahdi .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) :1037-1044
[6]  
*EPRI, 2006, PROT REL NUM PROT RE
[7]   ANFIS-Based Compensation Algorithm for Current-Transformer Saturation Effects [J].
Erenturk, Koksal .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (01) :195-201
[8]   Current transformer dimensioning for numerical protection relays [J].
Gangadharan, Pradeep Kumar ;
Sidhu, Tarlochan S. ;
Finlayson, Gregory James .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (01) :108-115
[9]   Compensation of Distorted Secondary Current Caused by Saturation and Remanence in a Current Transformer [J].
Hong, Ying-Yi ;
Wei, Da-Wei .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (01) :47-54
[10]  
Johns A. T., 1997, DIGITAL PROTECTION P