Event-driven optimal control of central air-conditioning systems: Event-space establishment

被引:21
作者
Wang, Junqi [1 ]
Jia, Qing-Shan [2 ]
Huang, Gongsheng [3 ]
Sun, Yongjun [1 ]
机构
[1] City Univ Hong Kong, Bldg Sci & Technol, Tat Chee Ave, Kowloon, Hong Kong, Peoples R China
[2] Tsinghua Univ, Dept Automat, Beijing, Peoples R China
[3] City Univ Hong Kong, Architecture & Civil Engn, Tat Chee Ave, Kowloon, Hong Kong, Peoples R China
关键词
BUILDING HVAC SYSTEMS; CHILLER PLANTS; WATER-SYSTEMS; OPTIMIZATION; ENERGY; STRATEGIES; PERFORMANCE; EFFICIENCY; OPERATION; MODELS;
D O I
10.1080/23744731.2018.1457410
中图分类号
O414.1 [热力学];
学科分类号
摘要
Real-time optimal control is widely adopted in central air-conditioning systems to improve the building energy management efficiency by adjusting system controllable variables according to system operating conditions. In time-driven optimal control, optimization actions are triggered periodically, which may not be efficient when the operating conditions of central air-conditioning systems are significantly irregular. To overcome this limitation, event-driven optimal control was proposed, in which optimization actions are triggered by "events" instead of a "clock". In event-driven optimal control, the definition of events are critical because "events" will directly affect the control efficiency and the online computational efficiency. In current literature, however, very few studies can be found on how to systematically establish a suitable event space for air-conditioning systems. This paper therefore presents a knowledge-based method for establishing event space. Case studies that were carried out in a typical commercial air-conditioning system is used to demonstrate the proposed method and its effectiveness, where real measured load and weather data were used.
引用
收藏
页码:839 / 849
页数:11
相关论文
共 47 条
[11]  
Cassandras C.G., 2014, Journal of Control and Decision, V1, P3, DOI [10.1080/23307706.2014.885288, DOI 10.1080/23307706.2014.885288]
[12]   An optimization strategy for the control of small capacity heat pump integrated air-conditioning system [J].
Gao, Jiajia ;
Huang, Gongsheng ;
Xu, Xinhua .
ENERGY CONVERSION AND MANAGEMENT, 2016, 119 :1-13
[13]  
Heemels W., 2015, Encyclopedia of Systems and Control, P384
[14]   Analysis of event-driven controllers for linear systems [J].
Heemels, W. P. M. H. ;
Sandee, J. H. ;
Van den Bosch, P. P. J. .
INTERNATIONAL JOURNAL OF CONTROL, 2008, 81 (04) :571-590
[15]  
Huang G., 2016, CLIMA 2016 12 REHVA
[16]   Improved cooling tower control of legacy chiller plants by optimizing the condenser water set point [J].
Huang, Sen ;
Zuo, Wangda ;
Sohn, Michael D. .
BUILDING AND ENVIRONMENT, 2017, 111 :33-46
[17]   Amelioration of the cooling load based chiller sequencing control [J].
Huang, Sen ;
Zuo, Wangda ;
Sohn, Michael D. .
APPLIED ENERGY, 2016, 168 :204-215
[18]   Event-driven optimal control of continuous Petri nets [J].
Júlvez, J ;
Bemporad, A ;
Recalde, L ;
Silva, M .
2004 43RD IEEE CONFERENCE ON DECISION AND CONTROL (CDC), VOLS 1-5, 2004, :69-74
[19]  
Karvigh S.A., 2017, ENERGY BUILDINGS
[20]   Uncertainty in developing supervisory demand-side controls in buildings: A framework and guidance [J].
Kim, Sean Hay ;
Augenbroe, Godfried .
AUTOMATION IN CONSTRUCTION, 2013, 35 :28-43