Numerical Analysis of the Effect of Converter Transformer Combined Magnetic Shielding on Stray Load Losses Considering DC Bias

被引:0
作者
Wang, Haoming [1 ]
Yang, Qingxin [1 ]
Li, Yang [1 ]
Li, Yongjian [1 ]
Zhang, Yue [2 ]
Wang, Jianmin [2 ]
机构
[1] Hebei Univ Technol, State Key Lab Reliabil & Intelligence Elect Equip, Tianjin 300130, Peoples R China
[2] Baoding Tianwei Baobian Elect Co Ltd, Baoding 071056, Peoples R China
基金
中国国家自然科学基金;
关键词
Magnetic shielding; stray load losses; converter transformer; DC bias;
D O I
10.1109/TASC.2021.3091102
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In order to accurately analyze the effect of combined magnetic shielding on stray load losses of converter transformer, a three-dimensional (3D) finite-element analysis (FEA) model is established. The total losses can be gotten by summing the simulated losses of each harmonic. The effectiveness of the presented simulation method is verified by comparing the simulated and tested stray load losses of the converter transformer in the case of rated operation without lobe-type magnetic shielding structure. Afterwards, the installation position of lobe-type magnetic shielding is optimized by considering its effect on stray load losses. Finally, the stray load losses under different DC bias currents are simulated and analyzed.
引用
收藏
页数:4
相关论文
共 10 条
[1]   An improved magnetostriction model of silicon steel considering the saturated magnetic domain wall movement [J].
Ben, Tong ;
Chen, Fangyuan ;
Chen, Long ;
Yan, Rongge .
AIP ADVANCES, 2021, 11 (01)
[2]   Detection Method of the DC Bias in Distribution Power Transformers [J].
Buticchi, Giampaolo ;
Lorenzani, Emilio .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (08) :3539-3549
[3]   Temperature rise of a dry-type transformer with quasi-3D coupled-field method [J].
Liu, Chao ;
Ruan, Jiangjun ;
Wen, Wu ;
Gong, Ruohan ;
Liao, Caibo .
IET ELECTRIC POWER APPLICATIONS, 2016, 10 (07) :598-603
[4]   Reduction of Stray Loss in Power Transformers Using Horizontal Magnetic Wall Shunts [J].
Moghaddami, Masood ;
Sarwat, Arif I. ;
de Leon, Francisco .
IEEE TRANSACTIONS ON MAGNETICS, 2017, 53 (02) :1-7
[5]   Numerical Calculation and Experimental Verification for Leakage Magnetic Field and Temperature Rise of Transformer Core Tie-Plate [J].
Wang, Haoming ;
Yang, Qingxin ;
Li, Yongjian ;
Wang, Jianmin ;
Zhao, Yinhan .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2019, 29 (02)
[6]   Research on Calculating Eddy-Current Losses in Power Transformer Tank Walls Using Finite-Element Method Combined With Analytical Method [J].
Yan, Xiuke ;
Yu, Xiangdong ;
Shen, Min ;
Xie, Dexin ;
Bai, Baodong .
IEEE TRANSACTIONS ON MAGNETICS, 2016, 52 (03)
[7]  
Yang X., 2016, IEEE MAGN LETT, V8
[8]   Queue-Aware Variable-Length Coding for Ultra-Reliable and Low-Latency Communications [J].
Zhao, Xiaoyu ;
Chen, Wei .
2019 IEEE GLOBAL COMMUNICATIONS CONFERENCE (GLOBECOM), 2019,
[9]   Measurements and Calculation of Core-Based B-H Curve and Magnetizing Current in DC-Biased Transformers [J].
Zhao, Zhigang ;
Liu, Fugui ;
Cheng, Zhiguang ;
Yan, Weili ;
Liu, Lanrong ;
Zhang, Junjie ;
Fan, Yana .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2010, 20 (03) :1151-1154
[10]   Computation of 3-D Magnetic Leakage Field and Stray Losses in Large Power Transformer [J].
Zhu, Zhanxin ;
Xie, Dexin ;
Wang, Gang ;
Zhang, Yanli ;
Yan, Xiuke .
IEEE TRANSACTIONS ON MAGNETICS, 2012, 48 (02) :739-742