Study on Application Method of Superconducting Fault Current Limiter for Protection Coordination of Protective Devices in a Power Distribution System

被引:27
作者
Kim, Jin-Seok [1 ]
Lim, Sung-Hun [1 ]
Kim, Jae-Chul [1 ]
机构
[1] Soongsil Univ, Dept Elect Engn, Seoul 156743, South Korea
基金
新加坡国家研究基金会;
关键词
Protective coordination; protective devices; superconducting fault current limiter (SFCL); time dial (TD);
D O I
10.1109/TASC.2011.2174551
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, the application method of superconducting fault current limiter (SFCL) for the protection coordination of the protective devices in a power distribution system was analyzed. The SFCL has been announced as better solution among many methods to limit a fault current effectively, which has continuously increased due to more complex network of a power system. However, the application of the SFCL in a power system affects the operation of the protection devices and the protection coordination, which requires the study on the protection coordination of the protective devices considering the application of the SFCL in a power distribution system. In this paper, the methods to maintain the protection operation of the protective devices due to the SFCL's application in a power distribution system were investigated through some case studies considering the time current curve (TCC) of the protection relay. The setting current and the lever among the setting parameters of the protective devices to keep the protection coordination in a power system with a SFCL were selected. Through the analysis on the TCC curves, the higher pick up current and the lower time lever values could be confirmed for protection coordination in case that the SFCL was introduced in the power system with the fixed impedance of the SFCL.
引用
收藏
页数:4
相关论文
共 13 条
[1]   Resistive current limiters with YBCO films [J].
Gromoll, B ;
Ries, G ;
Schmidt, W ;
Kramer, HP ;
Kummeth, P ;
Neumuller, HW ;
Fischer, S .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 1997, 7 (02) :828-831
[2]   Long-Term Operation and Fault Tests of a 22.9 kV Hybrid SFCL in the KEPCO Test Grid [J].
Hyun, Ok-Bae ;
Yim, Seong-Woo ;
Yu, Seung-Duck ;
Yang, Seong Eun ;
Kim, Woo-Seok ;
Kim, Hye-Rim ;
Lee, Gyeong-Ho ;
Sim, Jungwook ;
Park, Kwon-Bae .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2011, 21 (03) :2131-2134
[3]   Introduction of a Hybrid SFCL in KEPCO Grid and Local Points at Issue [J].
Hyun, Ok-Bae ;
Park, Kwon-Bae ;
Sim, Jungwook ;
Kim, Hye-Rim ;
Yim, Seong-Woo ;
Oh, Il-Sung .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2009, 19 (03) :1946-1949
[4]   Study on Protection Coordination of a Flux-Lock Type SFCL With Over-Current Relay [J].
Kim, J. S. ;
Lim, S. H. ;
Kim, J. C. .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2010, 20 (03) :1159-1163
[5]  
Kim JH, 2009, ARTECH HSE METH BIOE, P1, DOI 10.1109/ICIMW.2009.5324773
[6]   Study on Protective Coordination for Application of Superconducting Fault Current Limiter [J].
Kim, Jin-Seok ;
Lim, Sung-Hun ;
Kim, Jae-Chul .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2011, 21 (03) :2174-2178
[7]   Practical application issues of superconducting fault current limiters for electric power systems [J].
Lee, B. W. ;
Sim, J. ;
Park, K. B. ;
Oh, I. S. .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2008, 18 (02) :620-623
[8]  
Lee SR, 2006, TRANS DISTRIB CONF, P1144
[9]  
Sung-Hun Lim, 2007, Journal of Electrical Engineering & Technology, V2, P289, DOI 10.5370/JEET.2007.2.3.289
[10]  
Sung-Hun Lim, 2008, Journal of Electrical Engineering & Technology, V3, P213, DOI 10.5370/JEET.2008.3.2.213