Damping Control of HVDC Links to Mitigate Controller Interaction with Resonances of the Offshore Wind Farm

被引:0
作者
Korai, Abdulwahab [1 ]
Erlich, Istvan [1 ]
机构
[1] Inst Elect Power Syst, D-47057 Duisburg, Germany
来源
IFAC PAPERSONLINE | 2017年 / 50卷 / 01期
关键词
HVDC; offshore WF; Controller design; MVMO; Harmonic stability;
D O I
10.1016/j.ifacol.2017.08.015
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This paper deals with the harmonic instability problem in offshore wind farms caused by the interaction of HVDC controller with the resonance frequencies of the grid. Due to the HVDC filters, transformers and long submarine cables wind farms have natural resonances, which are close to the operating frequency of the HVDC converter. Even through the grid resonances exhibit inherent damping, the converter control may amplify the oscillations resulting in harmonic instability. Therefore, the converter control has to be designed properly taking into account all possible operating conditions and grid topologies. In this paper a new damping control approach is presented that is using the dq components of the current for modulating the converter output voltage. The parameters of the damping controller are estimated by the heuristic optimization algorithm MVMO simultaneously for three different disturbance scenarios. Simulation results in the time domain demonstrate the effectiveness of the proposed method. (C) 2017, IFAC (International Federation of Automatic Control) Hosting by Elsevier Ltd. All rights reserved.
引用
收藏
页码:85 / 89
页数:5
相关论文
共 6 条
[1]   Enhanced Voltage Drop Control by VSC-HVDC Systems for Improving Wind Farm Fault Ridethrough Capability [J].
Erlich, I. ;
Feltes, Ch ;
Shewarega, F. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (01) :378-385
[2]  
Erlich I., 2017, IEEE T ENERGY CONVER
[3]  
Erlich I., 2016, 2016 IEEE POW EN SOC
[4]  
Korai A, 2016, IFAC WORKSH CONTR TR
[5]  
Lukasz K., 2012, THESIS
[6]  
Rueda J, 2015, IEEE C EV COMP CEC 2