LITHIUM-ION BATTERY FIRE SUPPRESSION USING WATER MIST SYSTEMS

被引:5
作者
Ghiji, Matt [1 ]
Burch, Ian [2 ]
Suendermann, Brigitta [2 ]
Gamble, Grant [2 ]
Novozhilov, Vasily [1 ]
Joseph, Paul [1 ]
Moinuddin, Khalid [1 ]
机构
[1] Victoria Univ, Inst Sustainable Ind & Liveable Cities ISILC, Werribee Campus,POB 14428, Melbourne, Vic 8001, Australia
[2] Def Sci & Technol Grp, Maritime Div, 506 Lorimer St, Melbourne, Vic 3207, Australia
来源
FRONTIERS IN HEAT AND MASS TRANSFER | 2021年 / 17卷
关键词
Lithium-ion Battery; Thermal Runaway; Fire; Suppression; Water Mist; THERMAL RUNAWAY; BEHAVIOR; CELLS; EFFICIENCY; MECHANISM; ABUSE;
D O I
10.5098/hmt.17.13
中图分类号
O414.1 [热力学];
学科分类号
摘要
Lithium-ion batteries (LiBs) have superior energy density and lifetime compared to battery technologies such as lead acid. Despite the widespread application of LiBs in energy storage systems, electronic devices, aerospace and the automotive industry, they present a fire risk. In this study, experiments were conducted to characterize the thermal behavior of the electrolyte (as the main contributor to LiB fires) using a cone calorimeter; investigate the interactions of water mist and a Bunsen burner, as a precursor to examining the effectiveness of a water mist suppression system in extinguishing a LiB fire. In the present work, we have endeavored to systematically study the fire suppression efficacy of water mist by adopting to some novel approaches. This involved carefully planned laboratory scale explorations that involved a propane gas fueled flame, and subsequently by using bespoke set up that mimicked fire owing to fuel surge from typical Li-ion cell (18650 cells). In the latter set of fire suppression tests, water droplets were produced by a fan nozzle and sprayed horizontally toward the jet flame of replica 18560 battery containing only the electrolyte. The results showed that both fire types (Bunsen burner and LiB) are suppressed rapidly on activation of the water mist fire suppression system for geometries that enable the water mist direct access to the lift-off zone, between the gas source and base of the flame.
引用
收藏
页数:8
相关论文
共 50 条
[1]  
[Anonymous], 2015, 5660 ISO, DOI [10.3403/bsiso5660, DOI 10.3403/BSISO5660]
[2]   Battery separators [J].
Arora, P ;
Zhang, ZM .
CHEMICAL REVIEWS, 2004, 104 (10) :4419-4462
[3]   HEAT RELEASE RATE - THE SINGLE MOST IMPORTANT VARIABLE IN FIRE HAZARD [J].
BABRAUSKAS, V ;
PEACOCK, RD .
FIRE SAFETY JOURNAL, 1992, 18 (03) :255-272
[4]  
Blum Andrew F, 2016, FIRE HAZARD ASSESSME, DOI [10.1007/978-1-4939-6556-4, DOI 10.1007/978-1-4939-6556-4]
[5]  
Depetro A., 2016, Future Submarine Fire Safety Study
[6]  
Ditch B., 2013, Flammability characterization of lithium-ion batteries in bulk storage
[7]   Fire Fighting of Li-Ion Traction Batteries [J].
Egelhaaf, Markus ;
Kress, David ;
Wolpert, Dieter ;
Lange, Thomas ;
Justen, Rainer ;
Wilstermann, Hartung .
SAE INTERNATIONAL JOURNAL OF ALTERNATIVE POWERTRAINS, 2013, 2 (01) :37-48
[8]   Fire behavior of carbonates-based electrolytes used in Li-ion rechargeable batteries with a focus on the role of the LiPF6 and LiFSI salts [J].
Eshetu, Gebrekidan Gebresilassie ;
Bertrand, Jean-Pierre ;
Lecocq, Amandine ;
Grugeon, Sylvie ;
Laruelle, Stephane ;
Armand, Michel ;
Marlair, Guy .
JOURNAL OF POWER SOURCES, 2014, 269 :804-811
[9]   Thermal runaway mechanism of lithium ion battery for electric vehicles: A review [J].
Feng, Xuning ;
Ouyang, Minggao ;
Liu, Xiang ;
Lu, Languang ;
Xia, Yong ;
He, Xiangming .
ENERGY STORAGE MATERIALS, 2018, 10 :246-267
[10]  
Galarneau D, 2020, TRENDS STUDENT DEBT, P14