Mechanism analysis of unbalanced three-phase inrush current of Y0D transformer

被引:0
作者
Cao, Wenbin [1 ]
Qi, Xuanwei [1 ]
Huang, Xiaoming [1 ]
Chen, Ming [1 ]
Qiu, Yutao [2 ]
Yin, Xianggen [3 ]
机构
[1] State Grid Zhejiang Elect Power Res Inst, Hangzhou 310014, Peoples R China
[2] State Grid Zhejiang Power Co Ltd, Hangzhou 310007, Zhejiang, Peoples R China
[3] State Key Lab Adv Electromagnet Engn & Technol HU, Wuhan 430074, Peoples R China
关键词
High-impedance transformer; Imbalance; Circulating current; Dynamic phasor diagram;
D O I
10.1016/j.egyr.2022.03.019
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
During the energization of transformer with high-impedance (HT), the zero-sequence overcurrent protection (ZSOCP) often malfunction with the inrush current of primary winding (i(P-inrush)) shows a large unbalance. In order to clarify the cause of the misoperation and prepare for a solution, the imbalance characteristic is studied in this paper. The imbalance is visually displayed by dynamic phasor diagram. Through the method of numerical simulation, it can be obtained that the peak value of the zero-sequence current always appears near characteristic opening and switching angles (COSAs). At this time, the two phases are deep saturated and one phase is not saturated. The i(P-inrush) of the saturated phase is large, and that of the unsaturated phase is numerically the same as the circulating current (i(D)). According to the parameters characteristics of HT, the iD is small, so i(P) presents a large imbalance. The research conclusions provide a theoretical basis for zero-mode inrush current suppression. (c) 2022 Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/). Peer-review under responsibility of the scientific committee of the 2021 The 2nd International Conference on Power Engineering, ICPE, 2021.
引用
收藏
页码:1296 / 1304
页数:9
相关论文
共 4 条
  • [1] Three-Phase Asynchronous Motor Current Imbalance Detection and Analysis
    Zhou, Ai-Ai
    Liu, Shu-Xi
    Wu, Bo
    Wang, Kun-Jie
    Yang, Xiao-Duo
    INTERNATIONAL CONFERENCE ON CONTROL ENGINEERING AND AUTOMATION (ICCEA 2014), 2014, : 418 - 421
  • [2] Circulating Current Reduction for Three-Phase Back-to-Back Transformerless Inverter With SPWM-Based D-Σ Digital Control
    Wu, Tsai-Fu
    Lee, Po-Hung
    Lin, Li-Chiun
    Chang, Chih-Hao
    Chen, Yu-Kai
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2017, 32 (02) : 1591 - 1601
  • [3] Analysis on Circulating Current and Split Capacitor Voltage Balance for Modular Multilevel Converter Based Three-phase Four-wire Split Capacitor DSTATCOM
    Lin, Lei
    He, Jialu
    Xu, Chen
    JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, 2021, 9 (03) : 657 - 667
  • [4] Analysis on Circulating Current and Split Capacitor Voltage Balance for Modular Multilevel Converter Based Three-phase Four-wire Split Capacitor DSTATCOM
    Lei Lin
    Jialu He
    Chen Xu
    Journal of Modern Power Systems and Clean Energy, 2021, 9 (03) : 657 - 667