Energy and advanced exergy analyses of novel ejector-compressor partially coupled refrigeration cycle for buildings with less solar energy

被引:7
作者
Xu, Yingjie [1 ]
Huang, Songlin [1 ]
Wang, Jiafeng [1 ]
Song, Mengjie [2 ]
Yu, Jiaqi [1 ]
Shen, Xi [1 ]
机构
[1] Zhejiang Univ Technol, Coll Mech Engn, Engn Res Ctr Proc Equipment & Remfg, Minist Educ, Hangzhou 310014, Peoples R China
[2] Beijing Inst Technol, Sch Mech Engn, Dept Energy & Power Engn, Beijing 100081, Peoples R China
基金
中国国家自然科学基金;
关键词
MULTIOBJECTIVE OPTIMIZATION; HEAT-PUMP; SYSTEM; BEHAVIOR;
D O I
10.1063/5.0102885
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Solar-driven ejection-compression refrigeration is helpful for building space cooling but is based on the precondition of solar heat being infinite and free. This is not valid in many cases, such as multistorey buildings in metropolises with limited space. Even worse, in the carbon-neutral future, space surrounding buildings will be occupied by PV (photovoltaic) panels in priority. Therefore, a potential ejector-partially coupled enhanced compression refrigeration cycle consuming less heat is presented. Models of the new cycle for a multistorey building are established. Then, energy comparison and advanced exergy analysis are conducted. The analysis results first show that the new cycle needs no auxiliary system. Powered by limited low-grade heat, its C O P e increased by 20.66% and total annual cost reduced by 7.8%, compared with the traditional ejector-compressor cycle. Advanced exergy analysis also finds that the order of improvement potential is compressor (4739.45 W), evaporator (4329.85 W), and condenser (2843.51 W), according to the sum of avoidable exergy destruction. This is different from the results of conventional exergy analysis. The sensitivity analysis of the ejector components' efficiencies is investigated, which has seldom been reported for refrigeration system with ejector. The results reveal that once the efficiencies of ejector components reach a certain point (0.94), the performance no longer improves. Generally, this work provides a potential ejection-compression cycle, demonstrates system improvement direction through advanced exergy analysis, and reveals good understanding of the system. Published under an exclusive license by AIP Publishing.
引用
收藏
页数:19
相关论文
共 48 条
[21]   Energy, exergy and exergoeconomic analyses of a combined supercritical CO2 recompression Brayton/absorption refrigeration cycle [J].
Wu, Chuang ;
Wang, Shun-sen ;
Feng, Xue-jia ;
Li, Jun .
ENERGY CONVERSION AND MANAGEMENT, 2017, 148 :360-377
[22]   Modeling and Optimization of a Solar-Driven System Coupled with Liquid Dehumidification and Absorption Refrigeration Based on Advanced Exergy and Exergoeconomic Analyses [J].
Xu, Aixiang ;
Wang, Yizhang ;
Yang, Lanxiang ;
Luo, Xinyu ;
Song, Tingting ;
Liu, Zhiqiang ;
Yang, Sheng .
ACS SUSTAINABLE CHEMISTRY & ENGINEERING, 2023, 11 (22) :8386-8403
[23]   Design, exergy analysis, and optimization of a hydrogen generation/storage energy system with solar heliostat fields and absorption-ejector refrigeration system [J].
Musharavati, Farayi ;
Khanmohammadi, Shoaib ;
Mansir, Ibrahim B. .
INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2022, 47 (62) :25945-25963
[24]   Thermo-economic and advanced exergy analysis of a novel liquid carbon dioxide energy storage system coupled with solar energy and liquefied natural gas [J].
Liu, Zhongyan ;
Shao, Jiawei ;
Guan, Hongwei ;
Jin, Xu ;
Zhang, Hao ;
Li, Heng ;
Su, Wei ;
Sun, Dahan .
ENERGY, 2025, 315
[25]   Energy and exergy analyses of a recompression supercritical CO2 cycle combined with a double-effect parallel absorption refrigeration cycle [J].
Yousef, Mohamed S. ;
Santana, Domingo .
ENERGY REPORTS, 2023, 9 :195-201
[26]   Energy, modified exergy, exergo-economic and exergo-environmental analyses of a separation-enhanced auto-cascade refrigeration cycle [J].
Li, Yinlong ;
Chen, Qi ;
Liu, Guoqiang ;
Yan, Gang .
ENERGY CONVERSION AND MANAGEMENT, 2024, 299
[27]   Energy and Exergy Efficiency Analysis of an Ejector-Expansion Refrigeration Cycle Using the Working Fluid R134a and Its Potential Substitutes [J].
Liu, Xiaoqin ;
Wang, Weibin ;
Wang, Jianyong .
ENERGY SCIENCE & ENGINEERING, 2025, 13 (05) :2389-2400
[28]   Energy and exergy analyses of a novel near zero emission plant: Combination of MATIANT cycle with gasification unit [J].
Saeidi, S. ;
Mahmoudi, S. M. S. ;
Nami, H. ;
Yari, M. .
APPLIED THERMAL ENGINEERING, 2016, 108 :893-904
[29]   Parabolic trough solar collectors integrated with a Kalina cycle for high temperature applications: Energy, exergy and economic analyses [J].
Zare, V. ;
Moalemian, A. .
ENERGY CONVERSION AND MANAGEMENT, 2017, 151 :681-692
[30]   Advanced exergy, exergo-economic and exrgo-environmental analyses of a solar based trigeneration energy system [J].
Montazerinejad, Hadis ;
Ahmadi, Pouria ;
Montazerinejad, Zeynab .
APPLIED THERMAL ENGINEERING, 2019, 152 :666-685