Behavior of inhomogeneous high-temperature SF6 gas in a gas circuit breaker

被引:0
作者
Uchii, T [1 ]
Iwata, K [1 ]
Kawano, H [1 ]
Nakamoto, T [1 ]
Suzuki, K [1 ]
机构
[1] Toshiba Co Ltd, Kawasaki, Kanagawa 210, Japan
来源
2001 IEEE POWER ENGINEERING SOCIETY WINTER MEETING, CONFERENCE PROCEEDINGS, VOLS 1-3 | 2001年
关键词
gas circuit breaker; dielectric breakdown; hot gas; inhomogeneousness; dielectric capability; temperature; small gap;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The purpose of the present paper is to show the dielectric characteristics of inhomogeneous hot SF6 gas in a gas circuit breaker (GCB) experimentally. High-temperature and low-density SF6 gas generated by a heavy current interruption is distributed inhomogeneously in the grounded tank, and can strongly threaten the dielectric capability of the GCB. Few studies, however, have been carried out on the dielectric characteristics of the inhomogeneous hot gas. Using small gap discharges, the hot gas behavior of a GCB model, having breakdown or no breakdown, was investigated. The temperature of the hot gas flowing through the, exhaust tube was estimated from the sparking voltage of the small gap installed in the exhaust tube. It was also found that there was very little or no effect on breakdown voltages of the cool gas in the breakdown paths. This suggests that the breakdown voltage of inhomogeneous hot gas could be obtained as the applied voltage at which the electrical field strength equals E-crit of local hot gas at the location concerned.
引用
收藏
页码:289 / 294
页数:6
相关论文
共 50 条
[21]   Study on the Insulation Performance of SF6 Gas Under Different Environmental Factors [J].
An, Yunzhu ;
Yin, Kaiqiang ;
Huang, Tao ;
Hu, Yuanchao ;
Ma, Chenghui ;
Yang, Minghao ;
An, Bingchen ;
Chen, Dan .
FRONTIERS IN PHYSICS, 2022, 10
[22]   Influence of short-circuit current on motion characteristics of valves during breaking process of high-voltage auto-expansion SF6 circuit breaker [J].
Guo, Ze ;
Ma, Ping ;
Zhu, Kai ;
Li, Xingwen ;
Jia, Shenli .
Gaodianya Jishu/High Voltage Engineering, 2015, 41 (09) :3164-3170
[23]   Focused Shadowgraphy in the Heating Volume of a High-Voltage Gas Circuit Breaker [J].
Wiget, Roger ;
Lundqvist, Fredrik ;
Basse, Nils T. .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2011, 39 (11) :2852-2853
[24]   Development and Validation of Integrated High Voltage Gas Circuit Breaker Analysis Code [J].
Jung-Ho Park ;
Man-Jun Ha ;
Su-Hyun Park .
Journal of Electrical Engineering & Technology, 2021, 16 :3179-3188
[25]   Development and Validation of Integrated High Voltage Gas Circuit Breaker Analysis Code [J].
Park, Jung-Ho ;
Ha, Man-Jun ;
Park, Su-Hyun .
JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2021, 16 (06) :3179-3188
[26]   Fluoronitriles/CO2 Gas Mixture as Promising Substitute to SF6 for Insulation in High Voltage Applications [J].
Nechmi, H. E. ;
Beroual, A. ;
Girodet, A. ;
Vinson, P. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (05) :2587-2593
[27]   Effects of SF6 mixing ratio on DC positive streamer propagation in SF6/N2 gas discharge under a nonuniform electric field [J].
Li, Zhen ;
Sun, Yuanji ;
Zhang, Longfei ;
Gao, He ;
Wei, Yaoxin ;
Liu, Ji ;
Li, Shengtao .
AIP ADVANCES, 2024, 14 (01)
[28]   Modeling of Dynamic Characteristics for Spring Operating Gas Circuit Breaker [J].
Hashimoto, H. ;
Okubo, K. .
2014 IEEE PES T&D CONFERENCE AND EXPOSITION, 2014,
[29]   AN INVESTIGATION OF BREAKDOWN VOLTAGE WITH SMALL ARC CURRENT DUE TO POOR CONTACT IN SF6 GAS [J].
SUGIYAMA, S ;
MORITA, T ;
HOSOKAWA, T ;
SEKIYA, Y ;
MUKAIYAMA, Y ;
TAKAGI, I ;
LEE, KS .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (01) :332-338
[30]   Dielectric Properties of Fluoronitriles/CO2 and SF6/N2 Mixtures as a Possible SF6-Substitute Gas [J].
Zhao, Hu ;
Li, Xingwen ;
Tang, Nian ;
Jiang, Xu ;
Guo, Ze ;
Lin, Hui .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (04) :1332-1339