Flexible Fault Current Adaptation Features of a Novel DC Circuit Breaker Assisted by Superconducting Fault Current Limiters

被引:3
|
作者
Li, Hongxu [1 ]
Xiang, Bin [1 ]
Wang, Xuedong [1 ]
Li, Siyi [1 ]
Liu, Siyuan [1 ]
Geng, Yingsan [1 ]
Liu, Zhiyuan [1 ]
Wang, Jianhua [1 ]
机构
[1] Xi An Jiao Tong Univ, Dept Elect Engn, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
基金
中国国家自然科学基金;
关键词
Capacitors; Fault currents; Resistance; Circuit breakers; Integrated circuits; Voltage; Yttrium barium copper oxide; HVDC; DC circuit breaker; superconducting fault current limiter; quenching voltage of superconducting coils; MODEL;
D O I
10.1109/TPWRD.2021.3125498
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The high di/dt before zero-crossings easily leads to delayed or failed operations for the active current injection mechanical DC circuit breaker, especially for small direct current interruptions. The pre-charging process also makes this type of circuit breaker hard to realize repeat operations economically in the high voltage DC system. This paper proposes a novel DC circuit breaker and its design method that deeply coordinating a superconducting fault current limiter with the active current injection DC circuit breaker. This method significantly reduces di/dt before current zero-crossings and enables repeat operations economically. Besides limiting fault currents, the superconducting fault current limiter also charges the resonance capacitor flexibly in the circuit breaker, realizing the injected reverse current keep a constant proportion to the arbitrary fault current. Validations of the flexible capacitor charge and repeat operations are made by simulation and low voltage experiments. The charging times are within 2.5 ms and the reverse current keeps 1.2 to 1.7 times over the fault current under arbitrary conditions. Di/dt at current zero is reduced by 80% under 30% of rated interruption capacity. Flexible capacitor charge experiments are consistent with the simulation design. The superconducting tapes can recover within 300 ms to support repeat operations.
引用
收藏
页码:2348 / 2358
页数:11
相关论文
共 50 条
  • [21] Topology and Control of Multiport DC Circuit Breaker Integrating Current-Limiting and Fast Fault Clearing Capabilities
    Huang, Yunfeng
    Xiao, Huangqing
    Yang, Ping
    Huang, Ying
    IEEE TRANSACTIONS ON POWER DELIVERY, 2024, 39 (06) : 3199 - 3211
  • [22] Inductive fault current limiters: A review
    Heidary, Amir
    Radmanesh, Hamid
    Rouzbehi, Kumars
    Mehrizi-Sani, Ali
    Gharehpetian, Gevork B.
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 187
  • [23] Reinforcement Learning for Optimal Allocation of Superconducting Fault Current Limiters
    Ling, Xiejin
    Li, Yinhong
    2020 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2020,
  • [24] Fault isolation method of a hybrid HVDC system based on the coordination of a fault current limiter and a DC circuit breaker
    Chen L.
    He H.
    Wang L.
    Li G.
    Chen H.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2020, 48 (19): : 119 - 127
  • [25] Modeling and Simulation of Resistive Superconducting Fault-Current Limiters
    S. Nemdili
    S. Belkhiat
    Journal of Superconductivity and Novel Magnetism, 2012, 25 : 2351 - 2356
  • [26] Study on Superconducting Fault Current Limiters Based on Normal Transformers
    Chung, Dong Chul
    Pak, Byeong Ha
    Cho, Yong Sun
    Jung, Byung Ik
    Sung, Tae Hyn
    Choi, Hyo Sang
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2012, 22 (03)
  • [27] Recovery Characteristic of Coated Conductors for Superconducting Fault Current Limiters
    Berger, A.
    Noe, M.
    Kudymow, A.
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2011, 21 (03) : 1315 - 1318
  • [28] Sizing methodology for superconducting fault current limiters in HVDC grids
    Larruskain, D. Marene
    Etxegarai, Agurtzane
    Iturregi, Araitz
    Abarrategi, Oihane
    Eguia, Pablo
    2023 IEEE BELGRADE POWERTECH, 2023,
  • [29] Recovery in superconducting fault current limiters at low applied voltages
    Kim, Hye-Rim
    Yim, Seong-Woo
    Oh, Sung-Yong
    Hyun, Ok-Bae
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2008, 18 (02) : 656 - 659
  • [30] Development and Grid Operation of Superconducting Fault Current Limiters in KEPCO
    Kim, Hye-Rim
    Yang, Seong-Eun
    Yu, Seung-Duck
    Kim, Heesun
    Park, Byung-Jun
    Han, Young-Hee
    Park, Kijun
    Yu, Jaeun
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2014, 24 (05)