Effect of Soil Moisture on Arc Discharge in Sandy Soils Under Lightning Struck

被引:3
作者
Zhang, Bo [1 ]
Wang, Sen [2 ]
Wu, Jinpeng [1 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, Beijing 100084, Peoples R China
[2] Shaanxi Elect Power Res Inst, Xian 710048, Peoples R China
来源
IEEE LETTERS ON ELECTROMAGNETIC COMPATIBILITY PRACTICE AND APPLICATIONS | 2020年 / 2卷 / 04期
基金
中国国家自然科学基金;
关键词
Lightning; grounding; discharge; humidity; soil; ELECTRICAL BREAKDOWN; MODEL;
D O I
10.1109/LEMCPA.2020.3035072
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Onset electric field of arc discharge in soil is one of the basic parameters to analyze the lightning impulse performance of a grounding device. In this letter, a grounding rod is placed on the axis of a cylinder filled with sand, and an impulse current is applied between the grounding rod and the cylinder to simulate the electric field around the grounding rod under lightning strike. The transient current and potential are measured simultaneously with which, the onset electric field of arc discharge in sandy soils with different humidity and the time of discharge delay is obtained. Then, the effect and mechanism of the soil moisture on the arc discharge is discussed.
引用
收藏
页码:111 / 114
页数:4
相关论文
共 16 条
[1]  
[Anonymous], 1991, CIGRE WG01 SC33
[2]  
[Anonymous], 2018, IEC 62561-7
[3]   ELECTRICAL BREAKDOWN CHARACTERISTICS OF SOIL [J].
FLANAGAN, TM ;
MALLON, CE ;
DENSON, R ;
SMITH, I .
IEEE TRANSACTIONS ON NUCLEAR SCIENCE, 1982, 29 (06) :1887-1890
[4]   Progress in Lightning Impulse Characteristics of Grounding Electrodes With Soil Ionization [J].
He, Jinliang ;
Zhang, Bo .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2015, 51 (06) :4924-4933
[5]   Effective length of counterpoise wire under lightning current [J].
He, JL ;
Gao, YQ ;
Zeng, R ;
Zou, J ;
Liang, XD ;
Zhang, B ;
Lee, J ;
Chang, S .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :1585-1591
[6]   Study on X-Ray Imaging of Soil Discharge and Calculation Method of the Ionization Parameters [J].
Liu, Sanwei ;
Sima, Wenxia ;
Yuan, Tao ;
Luo, Donghui ;
Bai, Yang ;
Yang, Ming .
IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (04) :2013-2021
[7]   An engineering model for transient analysis of grounding system under lightning strikes: Nonuniform transmission-line approach [J].
Liu, YQ ;
Theethayi, N ;
Thottappillil, R .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :722-730
[8]   Integration of Energy Balance of Soil Ionization in CIGRE Grounding Electrode Resistance Model [J].
Mokhtari, Mehrdad ;
Gharehpetian, Gevork B. .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2018, 60 (02) :402-413
[9]   THE SOIL IONIZATION GRADIENT ASSOCIATED WITH DISCHARGE OF HIGH CURRENTS INTO CONCENTRATED ELECTRODES [J].
MOUSA, AM .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (03) :1669-1677
[10]   Determination of threshold electric field EC of soil under high impulse currents [J].
Nor, NM ;
Haddad, A ;
Griffiths, H .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (03) :2108-2113