Determination of Maximum Wind Power Penetration in an Isolated Island System by Considering Spinning Reserve

被引:11
作者
Chang, Chia-An [1 ,2 ]
Wu, Yuan-Kang [3 ]
Chen, Bin-Kwie [1 ]
机构
[1] Tatung Univ, Dept Elect Engn, Sect 3, Zhongshan North Rd, Taipei 10452, Taiwan
[2] Atom Energy Council, Inst Nucl Energy Res, Wenhua Rd, Taoyuan 32546, Taiwan
[3] Natl Chung Cheng Univ, Dept Elect Engn, Sect 1, Univ Rd, Chiayi 62102, Taiwan
关键词
wind power penetration; dispatching criteria; spinning reserve (SR); reliability and power quality; IMPACTS; TAIWAN; FARMS;
D O I
10.3390/en9090688
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The abundant wind resources in the Penghu area, where the capacity factor of wind turbines can reach 45%, have inspired authorities to build more wind turbines in a diesel-based power system. However, because the wind turbine output is unstable, high wind power penetration in the system may relatively affect the power quality (voltage and frequency) and reliability of the system. Previous studies have suggested that the optimal penetration level for wind power generation under the present dispatching criteria in Penghu is 26.3%. The present study suggests that the criteria for current unit scheduling should be modified; in particular, the spinning reserve (SR) capacity of the diesel engines should be increased without affecting the reliability and power quality of the power system. Such an increase could help avoid the construction of high-cost energy storage systems.
引用
收藏
页数:16
相关论文
共 32 条
[1]  
[Anonymous], 2012, NERC OP MAN
[2]  
[Anonymous], GLOB WIND STAT 2014
[3]  
Chanchien L. R., 2011, COMPREHENSIVE REPORT
[4]   A Novel Power System Defense Plan to Cope With 30% Wind Power Penetration in the Isolated Penghu System [J].
Chang, Chia-An ;
Wu, Yuan-Kang ;
Chen, Wei-Tai ;
Chen, Bin-Kwie .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2013, 49 (04) :1669-1677
[5]  
Chen B. K., 2008, STUDY WIND POWER PEN
[6]  
Chen B. K., 2012, WIND POWER PENETRATI
[7]  
DeMeo E. A., 2005, IEEE Power & Energy Magazine, V3, P38, DOI 10.1109/MPAE.2005.1524619
[8]   Sensitivity of personal computers to voltage sags and short interruptions [J].
Djokic, SZ ;
Desmet, J ;
Vanalme, G ;
Milanovic, JV ;
Stockman, K .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) :375-383
[9]   A new approach to quantify reserve demand in systems with significant installed wind capacity [J].
Doherty, R ;
O'Malley, M .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2005, 20 (02) :587-595
[10]  
Ellis J., 2012, ENERGY STORAGE WHY P