Experimental study of plate type air cooler performances under four operating modes

被引:30
作者
Chen, Yi [1 ]
Yang, Hongxing [1 ]
Luo, Yimo [2 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Renewable Energy Res Grp, Hong Kong, Hong Kong, Peoples R China
[2] Technol & Higher Educ Inst Hong Kong, Fac Sci & Technol, Hong Kong, Hong Kong, Peoples R China
关键词
Experiment; Energy recovery; Heat exchanger; Indirect evaporative cooler; Thermal performance; INDIRECT EVAPORATIVE COOLER; HEAT-EXCHANGERS; COOLING SYSTEM; WET CONDITIONS; FLOW; BUILDINGS; CONDENSATION; FEASIBILITY; MASS; DRY;
D O I
10.1016/j.buildenv.2016.05.022
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
To reduce the chiller energy consumption in a central air-conditioning system, a heat exchanger, acting as an air cooler, can be 'installed before an air handling unit to pre-cool the fresh air by recovering cooling capacity from exhaust air. However, studies on evaluating the performances of air cooler under condensation condition are limited. Therefore, an experimental study was conducted to evaluate the plate type air cooler performance under four operating modes (dry/wet mode, low/high air humidity). Under dry operating mode, the air cooler serves as a traditional air cooler; while under wet operating mode, it works as an indirect evaporative cooler (IEC). The cooler dynamic performances during different operating mode transition were investigated. The steady performances under different parameter influence were also comparatively studied. The results show that wet-operating improves the sensible and latent cooling capacities of air cooler significantly. Condensation takes place under high humidity inlet air, results in decreasing of sensible efficiency but increasing of latent efficiency and total heat transfer rate. The coefficient of performance (COP) of IEC is higher than that of traditional air cooler under the same testing configuration. The highest COP can reach 9.0 and achieved under wet operating mode with condensation. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:296 / 310
页数:15
相关论文
共 43 条
[1]   Analysis of heat-transfer performance of cross-flow fin-tube heat exchangers under dry and wet conditions [J].
An, Cheen Su ;
Choi, Do Hyung .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2012, 55 (5-6) :1496-1504
[2]  
[Anonymous], 2011, THESIS U NOTTINGHAM
[3]  
[Anonymous], 2008, ASHRAE HDB
[4]   Potential of the evaporative cooling techniques in the Gulf region of the Kingdom of Saudi Arabia [J].
Bajwa, Maqsood ;
Aksugur Erdal ;
Al-Otaibi, Ghazi .
Renewable energy, 1993, 3 (01) :15-29
[5]   Thermal comfort and energy consumption in a UK educational building [J].
Barbhuiya, Saadia ;
Barbhuiya, Salim .
BUILDING AND ENVIRONMENT, 2013, 68 :1-11
[6]  
Barbosa J., 2008, HEAT EXCHANGER DESIG, V98
[7]  
BARROW H, 1986, P 8 INT HEAT TRANSF, V2, P367
[8]  
Chen P. L., 1993, ASHRAE T 1, V99
[9]   Indirect evaporative cooler considering condensation from primary air: Model development and parameter analysis [J].
Chen, Yi ;
Yang, Hongxing ;
Luo, Yimo .
BUILDING AND ENVIRONMENT, 2016, 95 :330-345
[10]   A simplified analytical model for indirect evaporative cooling considering condensation from fresh air: Development and application [J].
Chen, Yi ;
Luo, Yimo ;
Yang, Hongxing .
ENERGY AND BUILDINGS, 2015, 108 :387-400