Structured modelling from data and optimal control of the cooling system of a large business center

被引:13
作者
Terzi, E. [1 ]
Fagiano, L. [1 ]
Farina, M. [1 ]
Scattolini, R. [1 ]
机构
[1] Politecn Milan, Dipartimento Elettron Informaz & Bioingn, I-20133 Milan, Italy
关键词
Cooling station; Control for energy saving; Identification; Modelling; Optimization; HVAC systems; PREDICTIVE CONTROL; HVAC SYSTEMS; OPTIMIZATION; SIMULATION;
D O I
10.1016/j.jobe.2019.101043
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The optimal cooling operation of a large business center, with five buildings totalling about 70,000 m(2) of interiors, is considered. This problem is relevant due to the high operational costs and energy demand of the cooling system. The latter features four chillers currently managed with heuristic rules. The aim of this study is to redesign the control system to minimize the energy consumption while still meeting the cooling demand. The main challenges are the impossibility to derive a model of the system based on physics, due to its high complexity and lack of information on each subsystem, and the on-off behavior and hysteretic operational constraints of the chillers. To solve this problem, a structured black-box dynamical model of the system is derived using machine learning techniques, exploiting a dataset of more than 500 days of operation. The employed quantities are easily measurable and include the flow rate and temperature of the cooling water, electric power consumption, and external temperature and humidity. Then, the derived model has been used to optimally tune the feedback control strategy via nonlinear programming, by minimizing the predicted energy consumption while satisfying the cooling demand. Simulation results with a validation dataset indicate that the proposed approach achieves an energy saving of 30% with respect to the controller currently adopted, while keeping the temperature in the desired range. The proposed modelling approach, based on data, results in a high applicability to plants with different layouts and components, whenever measurements of the relevant quantities are available.
引用
收藏
页数:11
相关论文
共 30 条
[1]   Development and performance comparison of low-order black-box models for a residential HVAC system [J].
Afram, Abdul ;
Fung, Alan S. ;
Janabi-Sharifi, Farrokh ;
Raahemifar, Kaamran .
JOURNAL OF BUILDING ENGINEERING, 2018, 15 :137-155
[2]   Energy consumption and efficiency in buildings: current status and future trends [J].
Allouhi, A. ;
El Fouih, Y. ;
Kousksou, T. ;
Jamil, A. ;
Zeraouli, Y. ;
Mourad, Y. .
JOURNAL OF CLEANER PRODUCTION, 2015, 109 :118-130
[3]  
Amara F., 2015, Smart Grid and Renewable Energy, V6, P95
[4]  
Ardabili SF, 2016, J BUILD ENG, V6, P301, DOI [10.1016/j.jobe.2016.04.010, 10.1016/j.jobc.2016.04.010]
[5]   Energy efficient control of HVAC systems with ice cold thermal energy storage [J].
Beghi, Alessandro ;
Cecchinato, Luca ;
Rampazzo, Mirco ;
Simmini, Francesco .
JOURNAL OF PROCESS CONTROL, 2014, 24 (06) :773-781
[6]  
Cengel Y.A., 2002, SEA, V1000, P8862
[7]  
Cigler Jiri, 2013, P 11 REHV WORLD C CL, P250
[8]   Approximate model predictive building control via machine learning [J].
Drgona, Jan ;
Picard, Damien ;
Kvasnica, Michal ;
Helsen, Lieve .
APPLIED ENERGY, 2018, 218 :199-216
[9]   Model predictive control strategy applied to different types of building for space heating [J].
Gholamibozanjani, Gohar ;
Tarragona, Joan ;
de Gracia, Alvaro ;
Fernandez, Cesar ;
Cabeza, Luisa F. ;
Farid, Mohammed M. .
APPLIED ENERGY, 2018, 231 :959-971
[10]  
Haves P., 2010, Model Predictive Control of HVAC Systems: Implementation and Testing at the University of California