Phasor measurement unit based transmission line protection scheme design

被引:28
作者
Zadeh, Hassan Khorashadi [1 ]
Li, Zuyi [2 ]
机构
[1] Siemens Energy Inc, Transmiss Div, Wendell, NC 27591 USA
[2] IIT, Dept Elect & Comp Engn, Chicago, IL 60616 USA
关键词
Global positioning system (GPS); Phasor measurement unit; Transmission line protection;
D O I
10.1016/j.epsr.2010.10.009
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents an adaptive transmission line protection scheme based on synchronized phasor measurement units. This scheme uses the positive-sequence voltage and current phasors at both ends of a transmission line to determine the parameter of the transmission line and the location of a fault on the transmission line. This scheme can be used for the protection of both single- and double-circuit transmission lines. This scheme is also robust against power swing conditions. A novel adaptive single pole auto re-closer is introduced based on the proposed scheme due to its capability of differentiating transient and permanent faults. System simulation studies show that the proposed scheme is able to operate fast and accurately for transmission line protection. (C) 2010 Elsevier B.V. All rights reserved.
引用
收藏
页码:421 / 429
页数:9
相关论文
共 17 条
[1]  
BHALJA B, 2005, P INT C COMP APPL EL, V1, P582
[2]  
BTTRNEL R, 1994, IEEE COMPUT APPL POW, V17, P8
[3]  
*EL TRAIN ASS, 1995, POW SYST PROT, V2
[4]   Design and implementation of an adaptive single pole autoreclosure technique for transmission lines using artificial neural networks [J].
Fitton, DS ;
Dunn, RW ;
Aggarwal, RK ;
Johns, AT .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (02) :748-756
[5]  
Horowitz SH, 2014, POWER SYSTEM RELAYIN
[6]  
ILAR F, 1997, B BOVERI PUBLICATION
[7]   IMPROVED TECHNIQUES FOR MODELING FAULT ARCS ON FAULTED EHV TRANSMISSION-SYSTEMS [J].
JOHNS, AT ;
AGGARWAL, RK ;
SONG, YH .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1994, 141 (02) :148-154
[8]  
KIMBARK E, 1997, POWER SYSTEM STABILI, V2
[9]  
MECHRAOUI A, 1993, UPEC 93, V2, P585
[10]   Arc characteristics and a single-pole auto-reclosure scheme for Alexandria HV transmission system [J].
Megahed, AI ;
Jabr, HM ;
Abouelenin, FM ;
Elbakry, MA .
ELECTRIC POWER SYSTEMS RESEARCH, 2006, 76 (08) :663-670