Theoretical model of buoyancy-driven air infiltration during heating/cooling seasons in large space buildings

被引:21
作者
Liu, Xiaochen [1 ]
Liu, Xiaohua [1 ]
Zhang, Tao [1 ]
机构
[1] Tsinghua Univ, Dept Bldg Sci, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
Large space building; Air infiltration; Theoretical model; Thermal stratification; Heating; Ventilation and air-conditioning (HVAC); INDOOR THERMAL ENVIRONMENT; NATURAL VENTILATION; MECHANICAL VENTILATION; SYSTEMS; CFD;
D O I
10.1016/j.buildenv.2020.106735
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Air infiltration is common in large space buildings during heating and cooling seasons, which leads to thermal discomfort and high energy consumption. However, there still lacks a valid theoretical model to analyze its mechanism and influence factors. In this study, a theoretical model of buoyancy-driven air infiltration in large space buildings is established with the factors of heating, ventilation and air-conditioning (HVAC) systems. The prediction results agree well with the field measurement and the numerical simulation. This model is used to analyze the influences of HVAC systems on air infiltration (i.e., thermal stratification and mechanical fresh/ exhaust air). A dimensionless buoyancy-driven force of air infiltration (C-T) is defined to quantify the thermal stratification. Compared with other typical terminal devices, the radiant floor has the lowest C-T in the heating and cooling conditions, which results in the lowest air infiltration rate. Besides, the air infiltration rate can theoretically decrease to zero with a sufficient mechanical fresh air rate of 1.4 times of the initial air infiltration rate, which is too large to realize in real buildings. This model helps to understand the air infiltration in large space buildings, which is beneficial to energy-efficient design and operation of HVAC systems.
引用
收藏
页数:12
相关论文
共 42 条
[1]  
Andersen KT, 1995, ASHRAE TRAN, V101, P1103
[2]  
ASHRAE, 2017, ASHRAE HDB FUND 2017, VSI
[3]  
Baturin V.V., 1953, AERATION OF INDUSTRI
[4]   Buoyancy-driven displacement natural ventilation in a single-zone building with three-level openings [J].
Chen, ZD ;
Li, YG .
BUILDING AND ENVIRONMENT, 2002, 37 (03) :295-303
[5]   Smoke control based on a solar-assisted natural ventilation system [J].
Ding, WT ;
Minegishi, Y ;
Hasemi, Y ;
Yamada, T .
BUILDING AND ENVIRONMENT, 2004, 39 (07) :775-782
[6]   Natural ventilation for passive cooling: measurement of discharge coefficients [J].
Flourentzou, F ;
Van der Maas, J ;
Roulet, CA .
ENERGY AND BUILDINGS, 1998, 27 (03) :283-292
[7]   Analysis of the influence of the return position in the vertical temperature gradient in displacement ventilation systems for large halls [J].
Gil-Lopez, Tomas ;
Galvez-Huerta, Miguel A. ;
O'Donohoe, Paul G. ;
Castejon-Navas, Juan ;
Dieguez-Elizondo, Pedro M. .
ENERGY AND BUILDINGS, 2017, 140 :371-379
[8]  
Haghighat F., 1989, International Journal of Ambient Energy, V10, P115
[9]   Experimental and CFD evidence of multiple solutions in a naturally ventilated building [J].
Heiselberg, P ;
Li, Y ;
Andersen, A ;
Bjerre, M ;
Chen, Z .
INDOOR AIR, 2004, 14 (01) :43-54
[10]   Measurements of indoor thermal environment and energy analysis in a large space building in typical seasons [J].
Huang, Chen ;
Zou, Zhijun ;
Li, Meiling ;
Wang, Xin ;
Li, Wei ;
Huang, Wugang ;
Yang, Jiangang ;
Xiao, Xueqin .
BUILDING AND ENVIRONMENT, 2007, 42 (05) :1869-1877