Effect of dusty atmosphere based on plastic powders on the operation of fire protection systems

被引:0
作者
Wnek, Waldemar [1 ]
机构
[1] Szkola Glowna Situzby Pozarniczej, Warsaw, Poland
来源
PRZEMYSL CHEMICZNY | 2017年 / 96卷 / 06期
关键词
D O I
10.15199/62.2017.6.13
中图分类号
O6 [化学];
学科分类号
0703 ;
摘要
Three corn. IR and UV fire detectors were used for testing fire protection systems in dusty spaces. Poly(We methactylate) dust (200-1000 pm size) was an object of the study. The detector response time decreased with decreasing dust grain size from 15 s down to 8 s. Two of the detectors recognized dust as a smoke and generated false fire alarm signal.
引用
收藏
页码:1284 / 1287
页数:4
相关论文
共 4 条
  • [1] Analysis of dust properties to solve the complex problem of non-fire sensitivity testing of optical smoke detectors
    Kruell, Wolfgang
    Schultze, Thorsten
    Tobera, Robert
    Willms, Ingolf
    [J]. 9TH ASIA-OCEANIA SYMPOSIUM ON FIRE SCIENCE AND TECHNOLOGY, 2013, 62 : 859 - 867
  • [2] Wnek W., 2011, WARSZTATY ZACISZE, V19, P7
  • [3] Wnek W., 2016, BITP, V42, P43
  • [4] Wnek W., 2015, SYSTEMY ALARMOWE, V5, P26