共 41 条
A new proposed dynamic arc model for flashover performance of a non-uniform polluted insulator string under HVAC stress
被引:11
|作者:
El-Zohri, Emad H.
[1
]
Ziedan, H.
[2
]
Prochazka, R.
[3
]
机构:
[1] Sohag Univ, Fac Ind Educ, Dept Elect, Sohag, Egypt
[2] Assiut Univ, Dept Elect Engn, Fac Engn, Assiut, Egypt
[3] Czech Tech Univ, Fac Elect Engn, CR-16635 Prague, Czech Republic
关键词:
Flashover mechanism;
Dynamic arc model;
Flashover voltage;
Leakage current;
HVAC stress;
Non-uniform polluted insulators;
AC VOLTAGE;
D O I:
10.1016/j.epsr.2014.10.005
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
This paper presents a new proposed dynamic arc model of a non-uniform polltited insulator under HVAC stress taking into account the dynamic arc characteristics. The model is based on a hybrid formulation of Obenaus model and the mathematical development of arc equations by Rizk combined with the dynamic equations of the change in arc resistance by Mayr. The model adopts the criterion of Hampton for arc propagation and the model is simulated using MATLAB Simulink. The model can calculate the instantaneous changes in arc current, arc length, arc resistance, and pollution level on insulator string at which the flashover occurs at certain voltage. Practical insulator geometries have been studied to demonstrate the model with non-uniform pollution in different positions and levels of pollution. The validity of the model is verified by comparing the simulation results with the experimental results and previous works. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:278 / 286
页数:9
相关论文