Humidity and contamination severity impact on the leakage currents of porcelain insulators

被引:37
|
作者
Li, J. Y. [1 ,2 ]
Sun, C. X. [1 ]
Sebo, S. A. [3 ]
机构
[1] Chongqing Univ, Coll Elect Engn, China State Key Lab Power Transmiss Equipment & S, Chongqing 400044, Peoples R China
[2] State Grid DC Project Construct Co Ltd, Beijing 100052, Peoples R China
[3] Ohio State Univ, Dept Elect & Comp Engn, Columbus, OH 43210 USA
关键词
CURRENT WAVE-FORMS; FREQUENCY-CHARACTERISTICS; FLASHOVER; VOLTAGE;
D O I
10.1049/iet-gtd.2009.0559
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The leakage current is the most important information for monitoring the insulator contamination, and especially for forecasting the contamination flashovers. Since the contamination severity and the ambient humidity can both result in the increase of the leakage currents, it is crucial to distinguish the exact reason for the leakage current changes. Experiments, repeated many times, have shown that the normal range of the leakage currents is less than 50 mA at rated operating voltage. This normal range is called the security stage, and it occurs far ahead of the contamination flashover. The characteristics of the leakage currents at that stage have been investigated when changes in the ambient humidity or the contamination severity were introduced in an artificial fog chamber. A joint approach of fast Fourier transform amplitude and power spectrum amplitude estimation is used to analyse the leakage currents in combination with the leakage current waveform. The main purpose is to improve the pre-warning of contamination flashover at the security stage and to obtain more time for the cleaning or replacement of heavily polluted insulators. Fog chamber test results show that there are two frequency spectrum related characteristics. Both characteristics play an important role in the state evaluation of insulator surface, considering the ambient humidity and the contamination severity. The pre-warning thresholds of these two characteristics can be recognised in case of very severe contamination together with high relative humidity conditions. These thresholds are very helpful for pre-warning in advance before contamination flashovers.
引用
收藏
页码:19 / 28
页数:10
相关论文
共 13 条
  • [1] Use of Leakage Currents of Insulators to Determine the Stage Characteristics of the Flashover Process and Contamination Level Prediction
    Li, Jingyan
    Sima, Wenxia
    Sun, Caixin
    Sebo, Stephen A.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (02) : 490 - 501
  • [2] Contamination Level Prediction of Insulators Based on the Characteristics of Leakage Current
    Li, Jingyan
    Sun, Caixin
    Sima, Wenxia
    Yang, Qing
    Hu, Jianlin
    IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (01) : 417 - 424
  • [3] Stage pre-warning based on leakage current characteristics before contamination flashover of porcelain and glass insulators
    Li, J. Y.
    Sun, C. X.
    Sima, W. X.
    Yang, Q.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2009, 3 (07) : 605 - 615
  • [4] Simulation of Contamination Deposition on Typical Shed Porcelain Insulators
    Lv, Yukun
    Zhao, Weiping
    Li, Jingang
    Zhang, Yazhao
    ENERGIES, 2017, 10 (07)
  • [5] Evaluating the contamination level of polluted insulators based on the characteristics of leakage current
    Zhao, Shihua
    Jiang, Xingliang
    Xie, Yanbin
    INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2015, 25 (10): : 2109 - 2123
  • [6] Anomalous Leakage Currents on Silicone Rubber Hollow Insulators
    Chrzan, Krystian Leonard
    Zipp, Maciej
    PRZEGLAD ELEKTROTECHNICZNY, 2020, 96 (10): : 91 - 93
  • [7] Mapping Relation of Leakage Currents of Polluted Insulators and Discharge Arc Area
    Fang, Chunhua
    Tao, Yuning
    Wang, Jianguo
    Ding, Can
    Huang, Li
    Zhou, Mi
    Gu, Yi
    Wang, Yali
    FRONTIERS IN ENERGY RESEARCH, 2021, 9
  • [8] Study on Pollution Severity of Porcelain Insulators Using LC and Phase Angle Measurement
    Chandrasekar, S.
    Kalaivanan, C.
    Karthikeyan, S.
    IEEE REGION 10 COLLOQUIUM AND THIRD INTERNATIONAL CONFERENCE ON INDUSTRIAL AND INFORMATION SYSTEMS, VOLS 1 AND 2, 2008, : 54 - 58
  • [9] Measurements and interpretations concerning leakage currents on polluted high voltage insulators
    Thalassinakis, E
    Karagiannopoulos, CG
    MEASUREMENT SCIENCE AND TECHNOLOGY, 2003, 14 (04) : 421 - 426
  • [10] Odd Harmonics and Third to Fifth Harmonic Ratios of Leakage Currents as Diagnostic Tools to Study the Ageing of Glass Insulators
    Bashir, N.
    Ahmad, H.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (03) : 819 - 832