Development of free-cooling detection procedures to support energy intelligence actions within telecommunication environments

被引:7
作者
Sorrentino, Marco [1 ]
Cirillo, Valentina [1 ]
Panagrosso, Davide [1 ]
Trifiro, Alena [2 ]
Bedogni, Filippo [2 ]
机构
[1] Univ Salerno, Dept Ind Engn, I-84084 Fisciano, SA, Italy
[2] Telecom Italia, Energy Grp Plans & Certificat, Rome, Italy
基金
英国工程与自然科学研究理事会;
关键词
Free-cooler detection; Diagnostics; Energy intelligence; Monitoring; Telecommunication; Thermal management; THERMAL MANAGEMENT; RISK MITIGATION; DATA CENTERS; PROGNOSTICS; SYSTEMS;
D O I
10.1016/j.applthermaleng.2018.08.048
中图分类号
O414.1 [热力学];
学科分类号
摘要
A signal-based diagnostic technique is proposed to enable remote monitoring of free-cooling (FC) systems operation in telecommunication (TLC) environments. The presented activity falls within a comprehensive energy intelligence action, which TIM-Telecom Italia has been carrying-on since more than a decade in its most strategic central offices and data centers. Main aim is to suitably exploit the available information, about temperature and electrical consumptions, so as to reduce its carbon footprint through strategic energy saving actions. The signal based procedure allows identifying in real-time what is the current status (i.e. properly working, not working or inefficient operation) of FCs in telecommunication rooms. Two alternative methodologies are proposed: one based on the analysis of temperature signal, through Discrete Fourier Transform (DFT), and the other on the evaluation of negative temperature time slope. This paper mostly focuses on the second methodology, which turned out to be the most effective one from a real-world deployability point of view. The results and experimental validation confirm the reliability and suitability of the proposed technique as an effective energy monitoring and diagnostic tool for TLC applications, to be deployed for leaner predictive maintenance tasks aimed at reducing FC failure dependent extra-costs. Further benefits include the synergies with control and/or supervisory energy management levels, which are expected to enable immediate counter-actions and upgrade current control logic, as well as the opportunity of supporting the execution of big-data energy intelligence actions within TLC central offices.
引用
收藏
页码:1037 / 1048
页数:12
相关论文
共 30 条
[1]  
Abolarinwa J. A., 2014, INT REV COMPUT SOFTW, V9, P1568
[2]  
Altman D. G., 2005, STANDARD DEVIATIONS
[3]  
[Anonymous], 2008, ASHRAE ENV GUIDELINE
[4]  
[Anonymous], KYOT PROT
[5]   A CFD analysis of an electronics cooling enclosure for application in telecommunication systems [J].
Boukhanouf, R. ;
Haddad, A. .
APPLIED THERMAL ENGINEERING, 2010, 30 (16) :2426-2434
[6]  
Commission of the European Communities, EUR STRAT EN TECHN P
[7]  
Curry E., 2012, P SUST INT ICT SUST
[8]   Reliability risk mitigation of free air cooling through prognostics and health management [J].
Dai, Jun ;
Das, Diganta ;
Ohadi, Michael ;
Pecht, Michael .
APPLIED ENERGY, 2013, 111 :104-112
[9]   Prognostics-based risk mitigation for telecom equipment under free air cooling conditions [J].
Dai, Jun ;
Das, Diganta ;
Pecht, Michael .
APPLIED ENERGY, 2012, 99 :423-429
[10]   A review of current status of free cooling in datacenters [J].
Daraghmeh, Hafiz M. ;
Wang, Chi-Chuan .
APPLIED THERMAL ENGINEERING, 2017, 114 :1224-1239