Contribution Mechanism and Impact Analysis of AC System at the Diode Natural Commutation and Conduction Stage During Bipolar Short-Circuit Fault for Single-Terminal VSC-Based DC Distribution Networks

被引:0
作者
Zhang, Zhihua [1 ]
Wang, Hao [1 ]
Wang, Kun [2 ]
Zhao, Yilong [3 ]
机构
[1] China Univ Petr, Coll New Energy, Qingdao 266580, Peoples R China
[2] State Grid Corp China, Laiwu Dist Power Supply Co, Qingdao 261000, Shandong, Peoples R China
[3] State Grid Corp China, Weifang Dist Power Supply Co, Qingdao 261000, Shandong, Peoples R China
基金
中国国家自然科学基金;
关键词
Circuit faults; Voltage; Transient analysis; Bridge circuits; Mathematical models; Distribution networks; Analytical models; Voltage source converter; single-terminal; bipolar short circuit; diodes natural commutation and conduction stage; contribution mechanism; impact analysis; PROTECTION SCHEME; LOCATION;
D O I
10.1109/ACCESS.2022.3190411
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
For single-terminal voltage source converter (VSC)-based DC distribution networks, the characteristics of bipolar short-circuit faults are a key factor for the design of protection schemes and the selection of power electronic devices. However, the contribution of AC systems is usually ignored at the diode natural commutation and conduction stage. There is no precise mathematical analysis model for this stage, and no influence mechanism of AC system has been demonstrated from theoretical perspective. This article presents a fault analysis model of the diode natural commutation and conduction stage, focusing on the transient feeding process of VSC converter during the bipolar short-circuit fault for single-terminal VSC-based DC distribution networks. According to equivalent circuits of different transient substages, accurate mathematical state equations are established. Expressions of each electrical fault variation during different substages are provided. A precise mathematical model is constructed, which considers the contribution mechanism of AC system at this stage. Then, based on this mathematical model, the influence of the AC system on electrical fault variations is analyzed from a theoretical perspective. The analysis results show that the influence is always small under different conditions and that ignoring the contribution of AC system can still meet actual engineering needs. A simulation model is constructed using MATLAB/Simulink software. The simulation results validate the effectiveness and superiority of the analysis model.
引用
收藏
页码:74082 / 74102
页数:21
相关论文
共 32 条
  • [1] A Reliable Protection Scheme for Fast DC Fault Clearance in a VSC-Based Meshed MTDC Grid
    Ara, Rifat
    Khan, Umer Amir
    Bhatti, Aamir Iqbal
    Lee, Bang Wook
    [J]. IEEE ACCESS, 2020, 8 : 88188 - 88199
  • [2] DC distribution for industrial systems: Opportunities and challenges
    Baran, ME
    Mahajan, NR
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2003, 39 (06) : 1596 - 1601
  • [3] Bin L, 2019, FAULT ANAL PROTECTIO, V3rd, P66
  • [4] [戴志辉 Dai Zhihui], 2018, [电工技术学报, Transactions of China Electrotechnical Society], V33, P1863
  • [5] An Advanced Protection Scheme for Enabling an LVDC Last Mile Distribution Network
    Emhemed, Abdullah A. S.
    Burt, Graeme M.
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2014, 5 (05) : 2602 - 2609
  • [6] [贾科 Jia Ke], 2018, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V38, P2883
  • [7] Lai XL, 2014, 2014 INTERNATIONAL ELECTRONICS AND APPLICATION CONFERENCE AND EXPOSITION (PEAC), P365, DOI 10.1109/PEAC.2014.7037883
  • [8] [李斌 Li Bin], 2015, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V35, P3026
  • [9] A Pole-to-Pole Short-Circuit Fault Current Calculation Method for DC Grids
    Li, Chengyu
    Zhao, Chengyong
    Xu, Jianzhong
    Ji, Yuke
    Zhang, Fan
    An, Ting
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (06) : 4943 - 4953
  • [10] Liu L., 2019, PROC IEEE 8 INT C AD, P21