The Effect of Surface Roughness on Corona-generated Electromagnetic Interference for Long-term Operating Conductors

被引:13
作者
Bian, Xingming [1 ,2 ,3 ]
Wang, Yuanjiu [4 ]
Wang, Liming [4 ]
Guan, Zhicheng [4 ]
Wan, Shuwei [5 ]
Chen, Lan [6 ]
Chen, Fangdong [6 ]
Zhao, Xuesong [6 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
[2] North China Elect Power Univ, Beijing Key Lab High Voltage, Beijing 102206, Peoples R China
[3] North China Elect Power Univ, EMC, Beijing 102206, Peoples R China
[4] Tsinghua Univ, Grad Sch Shenzhen, Shenzhen 518055, Guangdong, Peoples R China
[5] State Grid Chongqing Nanan Power Supply Co, Chongqing 400060, Peoples R China
[6] Jibei Elect Power Co Ltd, Beiijing 100053, Peoples R China
基金
中国国家自然科学基金;
关键词
AC corona discharge; electromagnetic interference; long-term operating conductor; surface condition; roughness; corona cage; VOLTAGE TRANSMISSION-LINES; RADIO-INTERFERENCE; INCEPTION VOLTAGES; AUDIBLE NOISE; FIELD; PREDETERMINATION; DISCHARGE; PERFORMANCE; PRESSURES; LEVEL;
D O I
10.1109/TDEI.2015.7076788
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a research of the surface roughness effects on corona-generated electromagnetic interference of long-term operating conductors. The detailed surface morphologies and roughness of typical long-term operating conductors were measured and analyzed. The radio noise measurement system based on the corona cage was discussed and the actual radio noise generated by the conductor in the measured cage was obtained, based on the parameters of the corona cage and the measured data. The radio noise tests were carried out under both dry and wet conditions. Under two types of conditions, the corona intensity was higher on the long-term operating conductors contrasted to the new conductors as a result of the anomalistic surfaces of the long-term operating conductors. The rate of decrease of corona inception voltages between the long-term operating conductors and new conductors was discovered to increase with the raise of surface roughness degree R-a in linear relationship. Approximate linear relation was also discovered between the averaged radio noise deviation and R-a. The rate of decrease of corona inception voltages under wet conditions was slightly higher (about 1%) than that under dry conditions. The difference between the radio noise of long-term operating conductors and that of new conductors was larger (1.3 dB) under wet conditions compared to dry conditions.