Estimation of shielding failure number of transmission lines for different trace configurations using leader progression analysis

被引:11
|
作者
Yahyaabadi, M. [2 ]
Vahidi, B. [1 ]
机构
[1] Amir Kabir Univ Technol, Dept Elect Engn, Tehran 1591634311, Iran
[2] Esfahan Reg Elect Co, Esfahan, Iran
关键词
Transmission line; Shielding failure; CSM; Leader progression; CHARGE SIMULATION METHOD; LIGHTNING PERFORMANCE; POWER-LINES; INCEPTION CRITERION; OVERHEAD LINES; ANALYSIS MODEL; EXPOSURE; STRIKES; STROKES;
D O I
10.1016/j.ijepes.2011.12.017
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The electrogeometric model (EGM) is a technique used for analyzing the termination of lightning flashes on transmission lines and masts, etc. When using the EGM for modeling the lightning stroke to transmission lines, the power line has normally been represented by a set of horizontal wire and both the sag of the wire, the existence of the towers and effect of uneven way have been ignored. This approach has serious short comings including inability to determine the percentage of the strokes terminating on the towers, failure to correctly predict the effect of height, and giving an approximate value for the number of collected strokes. This paper presents the development of a method for estimating the shielding failure number of power transmission lines in different trace configurations by using the charge simulation method. The effects of towers, sags of conductors, and a perfectly conducting ground are represented in 3-D computation. In addition, the stepwise descending nature of a downward negative leader-streamer systems taken into account by using an appropriate progression model. Upward leader inception and propagation is also modeled utilizing critical equivalent streamer-length criterion. The method is applied to compute the shielding failure of power transmission line for different trace configurations. In this paper the 3-D method is extended by modeling the effect of sloppy trace, trees on both and one side of the transmission line with extensive simulation results. Also, in this paper the effect of variation of tree height, its distance from transmission line and the number of trees on SFN are analyzed and results are shown in curves. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:27 / 32
页数:6
相关论文
共 39 条
  • [1] Estimation of shielding failure number of different configurations of double-circuit transmission lines using leader progression analysis model
    Yahyaabadi, M.
    Vahidi, B.
    Tavakoli, M. R. Bank
    ELECTRICAL ENGINEERING, 2010, 92 (02) : 79 - 85
  • [2] Estimation of shielding failure number of different configurations of double-circuit transmission lines using leader progression analysis model
    M. Yahyaabadi
    B. Vahidi
    M. R. Bank Tavakoli
    Electrical Engineering, 2010, 92 : 79 - 85
  • [3] Analysis of Lightning Shielding Failure for 500-kV Overhead Transmission Lines Based on an Improved Leader Progression Model
    Wei, Bengang
    Fu, Zhengcai
    Yuan, Haiyan
    IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) : 1433 - 1440
  • [4] An improved leader progression model for the analysis of the shielding performance of 1000 kV UHVAC transmission lines
    Wei, Bengang
    Fu, Zhengcai
    Yuan, Haiyan
    Du, Patrick Y.
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2010, 20 (03): : 327 - 335
  • [5] A Metamodeling Approach for Leader Progression Model-based Shielding Failure Rate Calculation of Transmission Lines Using Artificial Neural Networks
    Tavakoli, Mohammad Reza Bank
    Vahidi, Behrooz
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2011, 6 (06) : 760 - 768
  • [6] Leader progression analysis model for shielding failure computation by using the charge simulation method
    Vahid, Behrooz
    Yahyaabadi, Mostafa
    Tavakoli, Mohammad Reza Bank
    Ahadi, S. M.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) : 2201 - 2206
  • [7] Transmission-Lines Shielding Failure-Rate Calculation by Means of 3-D Leader Progression Models
    Tavakoli, Mohammad Reza Bank
    Vahidi, Behrooz
    IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (02) : 507 - 516
  • [8] Estimation of HVDC transmission lines shielding failure using LPM method and an adapted SLIM model
    Mohamadi, Reza
    Vahidi, Behrooz
    Rahiminejad, Abolfazl
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2019, 13 (09) : 1345 - 1351
  • [9] Comparison of numerical analysis models for shielding failure of transmission lines
    Wang, Xi
    Yu, Zhanqing
    Peng, Xiangyang
    Li, Zhifeng
    ELECTRIC POWER SYSTEMS RESEARCH, 2013, 94 : 71 - 78
  • [10] Analysis of Shielding Failure in Transmission Lines Considering Complex Terrain
    Yang, Qing
    Tao, Jiayuan
    Sima, Wenxia
    2017 INTERNATIONAL SYMPOSIUM ON LIGHTNING PROTECTION (XIV SIPDA), 2017, : 116 - 120