Modeling and Harmonic Optimization of a Two-Stage Saturable Magnetically Controlled Reactor for an Arc Suppression Coil

被引:103
作者
Chen, Xuxuan [1 ]
Chen, Baichao [1 ]
Tian, Cuihua [1 ]
Yuan, Jiaxin [1 ]
Liu, Yaozhong [1 ]
机构
[1] Wuhan Univ, Coll Elect Engn, Wuhan 430073, Peoples R China
基金
中国国家自然科学基金;
关键词
Arc suppression coil; harmonic analysis; magnetically controlled reactor (MCR); magnetic variable control; saturable reactor (SR); ACTIVE-POWER-FILTER; SYSTEMS;
D O I
10.1109/TIE.2011.2173090
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Magnetically controlled reactors (MCRs) are usually used as three-phase shunt reactors. They have low harmonic distortion independent of the third harmonic current because most three-phase MCRs are delta connected. However, as arc suppression coils, MCRs are operated in the single-phase mode, and the harmonics can be much higher than those of three-phase MCRs. In this paper, the structure and the mathematical model of a two-stage saturable MCR (TSMCR) are proposed. There are two stages with different lengths and areas in the iron cores. The stages saturate at different times when the TSMCR outputs reactive current. The current harmonics of the first saturated stage can be compensated for when the second stage begins to saturate, to reduce the total harmonics of the output current. The mathematical model that reveals the distribution characteristics of the current harmonics for the TSMCR is also presented. A study of the mathematical model indicates that there are two key factors that affect the total current harmonics of the TSMCR. One is the parameter k, which represents the area ratio of the second stage to the first stage. The other one is the parameter m, which represents the ratio of the length of the first stage to the total length of the magnetic valve in the iron core. The simulations and experiments show that the maximum current harmonics of the novel MCR can be limited to 3.61% of the rated output current when k and m are chosen according to the theoretical mathematical model.
引用
收藏
页码:2824 / 2831
页数:8
相关论文
共 23 条
[1]   Controlling linearity and permeability of iron core inductors using field orientation techniques [J].
Adly, AA .
IEEE TRANSACTIONS ON MAGNETICS, 2001, 37 (04) :2891-2893
[2]   Shunt active-power-filter topology based on parallel interleaved inverters [J].
Asiminoaei, Lucian ;
Aeloiza, Eddy ;
Enjeti, Prasad N. ;
Blaabjerg, Frede .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2008, 55 (03) :1175-1189
[3]  
Baichao Chen, 2000, APEC 2000. Fifteenth Annual IEEE Applied Power Electronics Conference and Exposition (Cat. No.00CH37058), P1066, DOI 10.1109/APEC.2000.822820
[4]   A SIMULATION-MODEL FOR THE SATURABLE REACTOR [J].
BARILI, A ;
BRAMBILLA, A ;
COTTAFAVA, G ;
DALLAGO, E .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 1988, 35 (02) :301-306
[5]   A Shunt Active Power Filter With Enhanced Performance Using ANN-Based Predictive and Adaptive Controllers [J].
Bhattacharya, Avik ;
Chakraborty, Chandan .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (02) :421-428
[6]  
BOHMANN LJ, 1990, IEEE T POWER DELIVER, V5, P1175, DOI 10.1109/61.53138
[7]   Minimising the risk of cross-country faults in systems using arc suppression coils [J].
Burgess, R. ;
Ahfock, A. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2011, 5 (07) :703-711
[8]   Comparison of thyristor-controlled reactors and voltage-source inverters for compensation of flicker caused by arc furnaces [J].
García-Cerrada, A ;
García-González, P ;
Collantes, R ;
Gómez, T ;
Anzola, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (04) :1225-1231
[9]   A case of abnormal overvoltages in a Petersen grounded 132-kV system caused by broken conductor [J].
Gustavsen, B ;
Walseth, JÅ .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (01) :195-200
[10]   Instantaneous Reactive Power Theory: A Reference in the Nonlinear Loads Compensation [J].
Herrera, Reyes S. ;
Salmeron, Patricio .