摘要
This paper aims to determine cost optimality between heating, ventilation and air conditioning (HVAC) systems operating with air to water heat pumps (AWHP) and water to water heat pumps (WWHP). The analysis is performed for a certain number of heat pump units with fixed and variable capacity made by four manufacturers available on European market. Simulations are performed in Trnsys software. The results show that heat pump partial load efficiency should not be neglected in analysis of application while the difference in energy consumption and costs can be up to 17%. The requirement for performing analysis on a wider range of units is indicated, especially when heat pump systems with different sources are considered. HVAC system with AWHP units with capacity control is a cost optimal solution for case study nursery building operating on the Croatian coast. The application of the photovoltaic (PV) array sized to cover nonrenewable part of electricity consumed in HVAC system has a return period of 12 years. It is determined that seasonal efficiency indicators from relevant European database do not support unit operation.
引用
收藏
页数:21
相关论文
共 31 条
  • [1] [Anonymous], 2017, 12831 EN
  • [2] [Anonymous], 2019, 148252019 EN
  • [3] [Anonymous], 1995, 1161995 ASHRAE
  • [4] [Anonymous], 2020, EN CROAT ANN EN REP
  • [5] [Anonymous], 2001, 10963 UNI
  • [6] [Anonymous], 2015, TECHN REG RAT US EN
  • [7] [Anonymous], 2012, COMMISSION DELEGATED
  • [8] ASHRAE, SERV LIF MAINT COST
  • [9] HVAC solutions for energy retrofitted hotel in Mediterranean area
    Becchio, Cristina
    Corgnati, Stefano Paolo
    Vio, Michele
    Crespi, Giulia
    Prendin, Leonardo
    Magagnini, Mattia
    [J]. CLIMAMED 2017 - MEDITERRANEAN CONFERENCE OF HVAC HISTORICAL BUILDINGS RETROFIT IN THE MEDITERRANEAN AREA, 2017, 133 : 145 - 157
  • [10] A review of performance of zero energy buildings and energy efficiency solutions
    Belussi, Lorenzo
    Barozzi, Benedetta
    Bellazzi, Alice
    Danza, Ludovico
    Devitofrancesco, Anna
    Fanciulli, Carlo
    Ghellere, Matteo
    Guazzi, Giulia
    Meroni, Italo
    Salamone, Francesco
    Scamoni, Fabio
    Scrosati, Chiara
    [J]. JOURNAL OF BUILDING ENGINEERING, 2019, 25