Thermal behaviour analysis of a high voltage inverted-type current transformer

被引:0
作者
Liao, Caibo [1 ]
Qiu, Zhibin [1 ]
Tang, Zhijian [1 ]
Li, Jiansheng [2 ]
Ma, Yong [2 ]
Zhang, Louxing [1 ]
Hou, Huasheng [1 ]
机构
[1] Nanchang Univ, Sch Informat Engn, 999 Xuefu Rd, Nanchang 330031, Jiangxi, Peoples R China
[2] State Grid Jiangsu Elect Power Res Inst, Nanjing, Peoples R China
关键词
current transformers; thermal analysis; temperature measurement; temperature distribution; FUNDAMENTAL APPROACH;
D O I
10.1049/elp2.12158
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A high voltage current transformer of the inverted type is a commonly used measurement equipment in power grids. The thermal behaviour of the current transformer has a significant impact on its operating conditions and is directly related to its service life. The study presents a three-dimensional simulation model of a 220 kV inverted-type oil-immersed current transformer, and the fluid and temperature field are analysed by the finite volume method. The simulation results show that the hot-spot temperature under the rated load of the calculation model introduced in the study is 61.5 degrees C, and located at the upper part of the core and the secondary winding. An experiment setup was designed to measure the temperature distribution inside a LVB-220W3-type current transformer. The temperature data measured under the rated load indicate that the simulation results agree well with the experimental results.
引用
收藏
页码:350 / 361
页数:12
相关论文
共 23 条
[1]   Solution algorithms for dynamic lot-sizing in remanufacturing systems [J].
Ahn, Hyung-Dae ;
Lee, Dong-Ho ;
Kim, Hwa-Joong .
INTERNATIONAL JOURNAL OF PRODUCTION RESEARCH, 2011, 49 (22) :6729-6748
[2]  
[Anonymous], 2010, 2084012010 GB
[3]  
[Anonymous], 2018, 6007672018 IEC
[4]  
[Anonymous], 2007, IEC 61869-1:2007
[5]  
[Anonymous], 1985, SHENYANG I TRANSFORM
[6]  
[Anonymous], 2012, IEEE Approved Draft Guide for Voltage Sag Indices
[7]   3-D Coupled Electromagnetic-Fluid-Thermal Analysis of Oil-Immersed Triangular Wound Core Transformer [J].
Liao, Caibo ;
Ruan, Jiangjun ;
Liu, Chao ;
Wen, Wu ;
Du, Zhiye .
IEEE TRANSACTIONS ON MAGNETICS, 2014, 50 (11)
[8]   Temperature rise of a dry-type transformer with quasi-3D coupled-field method [J].
Liu, Chao ;
Ruan, Jiangjun ;
Wen, Wu ;
Gong, Ruohan ;
Liao, Caibo .
IET ELECTRIC POWER APPLICATIONS, 2016, 10 (07) :598-603
[9]   Thermal Modeling of an Inverted-Type Oil-Immersed Current Transformer [J].
Mahajan, Satish M. ;
Robalino, Diego M. ;
Sivan, Vinod .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :2511-2518
[10]   INVERTED CURRENT TRANSFORMER [J].
MARKS, LW ;
SHADE, PV .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1967, PA86 (10) :1198-&