Numerical and Experimental Evaluation and Heat Transfer Characteristics of a Soft Magnetic Transformer Built from Laminated Steel Plates

被引:3
作者
Cano-Pleite, Eduardo [1 ]
Barrado, Andres [2 ]
Garcia-Hernando, Nestor [1 ]
Olias, Emilio [2 ]
Soria-Verdugo, Antonio [1 ]
机构
[1] Carlos III Univ Madrid Spain, Thermal & Fluids Engn Dept, Avda Univ 30, Leganes 28911, Spain
[2] Carlos III Univ Madrid Spain, Elect Technol Dept, Avda Univ 30, Leganes 28911, Spain
基金
欧盟地平线“2020”;
关键词
heat transfer; modeling; simulation; transformer; DRY-TYPE TRANSFORMER; TEMPERATURE DISTRIBUTION; VALIDATION; CONVECTION; MODEL;
D O I
10.3390/s21237939
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
The present work evaluates, both experimentally and numerically, the heat transfer characteristics of a 5 kW three-phase transformer built from laminated steel sheets. The transformer is operated at different powers, and its temperature distribution is monitored using 108 thermocouples. The experimental measurements are used firstly to determine the heat dissipated at the core and the windings of the transformer. This information is used as an input for a finite element numerical model, which evaluates the heat transfer characteristics of the transformer. The model proposed in this work simply solves the diffusion equation inside the transformer, accounting for the anisotropic thermal conductivity of the different components of the transformer, together with well-known correlations at its boundaries. The results reveal that the proposed numerical model can correctly reproduce the maximum temperature, the temperature distribution, and the time-evolution of the temperature at specific points of the transformer measured during the experimental campaign. These results are of great use for the subsequent development of transformers of the same type in lab-scale or industrial-scale size and reveal the applicability of simplified numerical models to accurately predict the heat transfer characteristics of this kind of transformers.
引用
收藏
页数:18
相关论文
共 32 条
[1]   Transformer Bushing Thermal Model for Calculation of Hot-Spot Temperature Considering Oil Flow Dynamics [J].
Akbari, Milad ;
Rezaei-Zare, Afshin .
IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (03) :1726-1734
[2]   An improved computational approach for thermal modeling of power transformers [J].
Allahbakhshi, Mehdi ;
Akbari, Asghar .
INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2015, 25 (07) :1319-1332
[3]   Recent progress in Fe-based amorphous and nanocrystalline soft magnetic materials [J].
Azuma, Daichi ;
Ito, Naoki ;
Ohta, Motoki .
JOURNAL OF MAGNETISM AND MAGNETIC MATERIALS, 2020, 501
[4]  
Balci S, 2014, 2014 16TH INTERNATIONAL POWER ELECTRONICS AND MOTION CONTROL CONFERENCE AND EXPOSITION (PEMC), P861, DOI 10.1109/EPEPEMC.2014.6980606
[5]  
Bertin Y., 1999, REFROISSEMENT MACHIN
[6]   Evolution and Modern Approaches for Thermal Analysis of Electrical Machines [J].
Boglietti, Aldo ;
Cavagnino, Andrea ;
Staton, David ;
Shanel, Martin ;
Mueller, Markus ;
Mejuto, Carlos .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2009, 56 (03) :871-882
[7]  
Chen YF, 2019, INT C ELECTR MACH SY, P4554
[8]  
CHURCHILL SW, 1975, INT J HEAT MASS TRAN, V18, P1323, DOI [10.1016/0017-9310(75)90243-4, 10.1016/0017-9310(75)90222-7]
[9]  
COMSOL AB, STOCKH SWED COMSOL M
[10]   A Transformer Thermal Model for use in an on-line Monitoring and Diagnostic System [J].
Elmoudi, Asaad ;
Palola, Jussi ;
Lehtonen, Matti .
2006 IEEE/PES POWER SYSTEMS CONFERENCE AND EXPOSITION. VOLS 1-5, 2006, :1092-+