The influence of the thickness of an aluminium radiant sheet on the performance of the lightweight floor heating

被引:17
作者
Werner-Juszczuk, Anna Justyna [1 ]
机构
[1] Bialystok Tech Univ, Heating Ventilat, Air Conditioning Dept, Wiejska 45E, PL-15351 Bialystok, Poland
来源
JOURNAL OF BUILDING ENGINEERING | 2021年 / 44卷
关键词
Radiant floor; Aluminium radiant sheet; Dry floor heating system; Lightweight floor heating; Numerical study; SURFACE-TEMPERATURE; NUMERICAL-ANALYSIS; SYSTEM; UNDERFLOOR; BUILDINGS; MODEL; PUMP;
D O I
10.1016/j.jobe.2021.102896
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The aim of this work is to determine the optimal thickness of aluminium radiant sheet in the lightweight floor heating, i.e. the smallest thickness of the aluminium, ensuring high efficiency and thermal comfort. The optimal operational and construction parameters are determined regards to the aluminium thickness. Finding the optimal aluminium thickness is important for economic and ecological reasons: less aluminium thickness, less aluminium consumption and less cost of construction. Numerical calculations were performed with ANSYS Steady-State Thermal Solver (Workbench 19.2) for floor heating with a dry screed, wood-like board and pipes embedded in the layer of tile adhesive. The influence of aluminium thickness changes in the range of 0.1-0.5 mm was analysed for variable water temperature, pipe spacing and constructions. The optimal aluminium radiant sheet thickness is 0.3 mm, 0.1 mm is not recommended. The optimal water temperature is 25-35 degrees C, 45 degrees C is not recommended. Constructions with a dry screed 25 mm thick should not be used. Constructions with pipes in tile adhesive should be used at a water temperature of 25-30 degrees C and an aluminium thickness of 0.3-0.5 mm. Constructions with wood-like board should be used at a water temperature of 25-35 degrees C and an aluminium of 0.3-0.4 mm. Results enable a conscious choice of such constructions and operational parameters of lightweight floor heating that ensure high efficiency, thermal comfort and low investment costs. The work includes the original specification of the lightweight floor heating efficiency depending on the radiant sheet thickness and specifies recommended radiant sheet thicknesses.
引用
收藏
页数:15
相关论文
共 50 条
  • [21] Design of radiant floor heating panel in view of floor surface temperatures
    Shin, Mi Su
    Rhee, Kyu Nam
    Ryu, Seong Ryong
    Yeo, Myoung Souk
    Kim, Kwang Woo
    BUILDING AND ENVIRONMENT, 2015, 92 : 559 - 577
  • [22] Experimental and numerical study on the heat transfer performance of the radiant floor heating condenser with composite phase change material
    Jiang, Tingting
    Zheng, Chenxiao
    You, Shijun
    Zhang, Huan
    Wu, Zhenjing
    Wang, Yaran
    Wei, Shen
    APPLIED THERMAL ENGINEERING, 2022, 213
  • [23] Simplified calculation for cooling/heating capacity, surface temperature distribution of radiant floor
    Zhang, Lun
    Liu, Xiao-Hua
    Jiang, Yi
    ENERGY AND BUILDINGS, 2012, 55 : 397 - 404
  • [24] Advancements in design of radiant floor heating systems with an innovative simplified calculation method
    Wang, Meijie
    Wang, Jiali
    Xu, Jiawei
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2025, 31 (01) : 112 - 125
  • [25] Model establishment and operation optimization of the casing PCM radiant floor heating system
    Lu, Shilei
    Gao, Jingxian
    Tong, Haojie
    Yin, Shuai
    Tang, Xiaolei
    Jiang, Xiangyang
    ENERGY, 2020, 193 : 1208 - 1224
  • [26] Study on heating capacity and heat loss of capillary radiant floor heating systems
    Ding, Pei
    Li, Yanru
    Long, Enshen
    Zhang, Yin
    Liu, Qinjian
    APPLIED THERMAL ENGINEERING, 2020, 165
  • [27] An RC-network model in the frequency domain for radiant floor heating coupled with envelopes
    Lu, Lidi
    Chen, Jinhua
    Su, Tao
    Liu, Xingyu
    Hu, Yaqi
    Luo, Qing
    Luo, Lulin
    BUILDING AND ENVIRONMENT, 2022, 225
  • [28] Field investigations on operational performance of a novel radiant floor heating equipment applied in a typical office building
    Qiao, Guinan
    Wang, Yu
    Yu, Haiyang
    Li, Yanju
    Guo, Chunmei
    BUILDING SERVICES ENGINEERING RESEARCH & TECHNOLOGY, 2022, 43 (02) : 207 - 223
  • [29] Thermal performance analysis according to wood flooring structure for energy conservation in radiant floor heating systems
    Seo, Jungki
    Jeon, Jisoo
    Lee, Jeong-Hun
    Kim, Sumin
    ENERGY AND BUILDINGS, 2011, 43 (08) : 2039 - 2042
  • [30] Analysis on the thermal performance of low-temperature radiant floor coupled with intermittent stratum ventilation (LTR-ISV) for space heating
    Kong, Xiangfei
    Chang, Yufan
    Fan, Man
    Li, Han
    ENERGY AND BUILDINGS, 2023, 278