Characteristic Analysis of Subsynchronous Resonance in Practical Wind Farms Connected to Series-Compensated Transmissions

被引:290
作者
Xie, Xiaorong [1 ]
Zhang, Xu [1 ]
Liu, Huakun [1 ]
Liu, Hui [2 ]
Li, Yunhong [2 ]
Zhang, Chuanyu [1 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, State Key Lab Power Syst, Beijing 100084, Peoples R China
[2] North China Elect Power Res Inst, Beijing 100045, Peoples R China
基金
中国国家自然科学基金;
关键词
Doubly fed induction generator (DFIG); permanent magnet synchronous generator (PMSG); series compensation; subsynchronous control interaction (SSCI); subsynchronous resonance (SSR); MITIGATING SSR; GENERATOR; CONTROLLER; STATCOM;
D O I
10.1109/TEC.2017.2676024
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The emerging subsynchronous resonance (SSR) caused by the interaction of wind turbine generators (WTGs) with series compensation has aroused great concerns. For this particular issue, this paper is aimed to fill the gap between theoretical studies and actual observations. By analyzing the field data of 58 SSR events captured in a practical wind power system and examining the observed dynamics with previous theoretical results, the mechanism and characteristics of SSR are revealed in a more explicit and substantial way. The necessary conditions and dominant influential factors are identified and the underlying reasons are discovered. Theoretically derived as well as practically measured impedance models have demonstrated that the converter control of doubly fed induction generator (DFIG) produces negative resistance at the slip frequency and thus causes unstable SSR; while permanent magnet synchronous generators and self-excited induction generators are just passively engaged in those SSR incidents. The distribution of the oscillation frequency has also been examined with field measurements. It is discovered that WTGs at different locations participate into the same SSR mode and their frequencies are not fixed but keep changing with the time, the variation of grid topology, and the number of online generators.
引用
收藏
页码:1117 / 1126
页数:10
相关论文
共 39 条
  • [31] Impedance-Based Stability Criterion for Grid-Connected Inverters
    Sun, Jian
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2011, 26 (11) : 3075 - 3078
  • [32] Suriyaarachchi DHR, 2012, IEEE POW ENER SOC GE
  • [33] A Procedure to Study Sub-Synchronous Interactions in Wind Integrated Power Systems
    Suriyaarachchi, D. H. R.
    Annakkage, U. D.
    Karawita, C.
    Jacobson, D. A.
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (01) : 377 - 384
  • [34] Mitigation of subsynchronous resonance in a series-compensated wind farm using FACTS controllers
    Varma, Rajiv K.
    Auddy, Soubhik
    Semsedini, Ysni
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (03) : 1645 - 1654
  • [35] Vieto I., 2015, Proceedings of 14th Wind Integration Workshop, P438
  • [36] Investigation of SSR in Practical DFIG-Based Wind Farms Connected to a Series-Compensated Power System
    Wang, Liang
    Xie, Xiaorong
    Jiang, Qirong
    Liu, Hui
    Li, Yu
    Liu, Huakun
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (05) : 2772 - 2779
  • [37] Minimizing the Circulation Current in Hexagram Medium-Voltage Variable-Speed Drive by Coupled Inductors
    Wen, Jun
    Zhou, Liang
    Smedley, Keyue
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (08) : 3421 - 3430
  • [38] Development and Field Experiments of a Generator Terminal Subsynchronous Damper
    Xie, Xiaorong
    Wang, Liang
    Guo, Xijiu
    Jiang, Qirong
    Liu, Quan
    Zhao, Yonglin
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (04) : 1693 - 1701
  • [39] Zhu CX, 2010, IEEE POW ENER SOC GE