Annual Energy Consumption Cut-Off with Cooling System Design Parameter Changes in Large Office Buildings

被引:5
|
作者
Ha, Ju-wan [1 ]
Cho, Soolyeon [2 ]
Kim, Hwan-yong [3 ]
Song, Young-hak [3 ]
机构
[1] Gyeongsang Natl Univ, Grad Sch, Dept Architectural Engn, Jinju 52828, South Korea
[2] North Carolina State Univ, Sch Architecture, Coll Design, Raleigh, NC 27695 USA
[3] Gyeongsang Natl Univ, Dept Architectural Engn, ERI, Jinju 52828, South Korea
基金
新加坡国家研究基金会;
关键词
large office; chilled water; cooling tower control; low-temperature condenser water; energy consumption; PERFORMANCE;
D O I
10.3390/en13082034
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
A variety of greenhouse gas reduction scenarios have been proposed around the world to ensure sustainable developments and strengthen the global response to the climate change. To cope with this, it is urgently needed to reduce the amount of energy used for the heating, ventilating, air conditioning, and refrigerating (HVAC&R) systems in large buildings. This study discusses the reduction of cooling energy in large office buildings through the minimization of changes in components and equipment, such as heat source equipment and pumps, changes in the layout and operating methods of chilled water circulation pumps, and changes in the temperatures of chilled and condenser water. To do this, this study targeted an entire cooling system consisting of a hydronic system, a chiller, and a cooling tower, and conducted a quantitative analysis of the energy consumption and of the reduction achieved through a change in the pumping system type in the cooling system and a change in the Korean standard design and temperature of chiller and cooling tower via EnergyPlus simulations. The simulation results showed a cooling energy reduction of 103.2 MWh/yr, around 15.7%, where the primary constant-speed system (Case A) was changed to a primary variable-speed pump (Case B) in the configuration with a chilled water circulation pump. To reduce the cooling energy further, annually 142.3 MWh, around 21.7%, Case C in this study changed the outlet temperature of the chiller and temperature difference from 7 degrees C, 5 K to 9 degrees C, 9 K. Finally, when applying a change in the condenser water production temperature from 32 to 23.9 degrees C in accordance with ASHRAE Standard 90.1 for Case D, a cooling energy saving of 182.4 MWh/yr was observed, which is about 27.8%.
引用
收藏
页数:16
相关论文
共 26 条
  • [1] Energy consumption of a novel floor radiant cooling system in large space buildings
    Du, Haiyi
    Shi, Juan
    Chen, Shengpeng
    Cheng, Siyuan
    Chen, Zhenqian
    APPLIED THERMAL ENGINEERING, 2024, 257
  • [2] Machine learning for occupant-behavior-sensitive cooling energy consumption prediction in office buildings
    Amasyali, Kadir
    El-Gohary, Nora
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2021, 142
  • [3] Development of a Metamodel to Predict Cooling Energy Consumption of HVAC Systems in Office Buildings in Different Climates
    Lopes, Mauricio Nath
    Lamberts, Roberto
    SUSTAINABILITY, 2018, 10 (12)
  • [4] Solar assisted desiccant evaporative cooling system for office buildings in Iran: An annual simulation model
    Ahmadzadehtalatapeh, M.
    SCIENTIA IRANICA, 2018, 25 (01) : 280 - 298
  • [5] Energy consumption modelling of a passive hybrid system for office buildings in different climates
    Zhang, Yi
    Tennakoon, Thilhara
    Chan, Yin Hoi
    Chan, Ka Chung
    Fu, Sau Chung
    Tso, Chi Yan
    Yu, Kin Man
    Huang, Bao Ling
    Yao, Shu Huai
    Qiu, Hui He
    Chao, Christopher Y. H.
    ENERGY, 2022, 239
  • [6] Energy efficiency and thermal comfort characteristics of convection-radiation combined cooling system in office buildings
    Liu, Dong
    Liu, Na
    Li, Guanyu
    Wu, Xiaozhou
    Wang, Jun
    Tian, Yabin
    Zhang, Qing
    Hu, Anjie
    Wen, Jialan
    JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, 2024, 38 (05) : 2649 - 2660
  • [7] Different responses of cooling energy consumption in office buildings to climatic change in major climate zones of China
    Li, Mingcai
    Cao, Jingfu
    Xiong, Mingming
    Li, Ji
    Feng, Xiaomei
    Meng, Fanchao
    ENERGY AND BUILDINGS, 2018, 173 : 38 - 44
  • [8] Research of design features that influence energy consumption in office buildings in Belo Horizonte, Brazil
    de Oliveira Veloso, Ana Carolina
    Goncalves de Souza, Roberta Vieira
    Nassar Koury, Ricardo Nicolau
    8TH INTERNATIONAL CONFERENCE ON SUSTAINABILITY IN ENERGY AND BUILDINGS, SEB-16, 2017, 111 : 111 - 120
  • [9] Performance and energy consumption estimation for commercial off-the-shelf component system design
    Andrade, Ermeson
    Maciel, Paulo
    Falcao, Tiago
    Nogueira, Bruno
    Araujo, Carlos
    Callou, Gustavo
    INNOVATIONS IN SYSTEMS AND SOFTWARE ENGINEERING, 2010, 6 (1-2) : 107 - 114
  • [10] A Method to be Use for Defining Effect of Environmental Friendly Facade Design Parameters on Energy Consumption for Office Buildings
    Uslusoy Senyurt, Selma
    Altin, Mujde
    MEGARON, 2020, 15 (01): : 55 - 66