On criteria of optimized application of AMF- and RMF-contact systems in vacuum interrupters

被引:0
作者
Renz, R [1 ]
机构
[1] Siemens AG, Berlin, Germany
来源
ISDEIV: XIXTH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, VOLS 1 AND 2, PROCEEDINGS | 2000年 / 19卷
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In case of interrupting high ac-currents in vacuum, a metal vapour are burns between the separating contacts, till the next current-zero. However, if the current exceeds the range of approximately 10 kA the are will pinch due to its own magnetic field. In order to avoid a local contact overheating there are two possibilities: Movement of the constricted are on the contact surface by a radial magnetic field (RMF) Prevention of are constriction by an axial magnetic field (AMF) In a short overview the functional principles and physics of RMF and AMF are given. Pros and cons of RMF versus AMF with regard to interrupting capability, electrical resistance, tubes dimension and production costs will be compared for the low, medium and high voltage range.
引用
收藏
页码:176 / 179
页数:4