Experimental Analysis of the R744/R404A Cascade Refrigeration System with Internal Heat Exchanger. Part 1: Coefficient of Performance Characteristics

被引:15
作者
Jeon, Min-Ju [1 ]
机构
[1] Chonnam Natl Univ, Coll Engn, Dept Refrigerat & Air Conditioning Engn, 50 Daehak Ro, Yeosu 59626, South Korea
关键词
cascade refrigeration system (CRS); R744; refrigerant; R404A refrigerant; internal heat exchanger (IHE); coefficient of performance (COP); efficiency; multilinear regression analysis; THERMODYNAMIC ANALYSIS; TEMPERATURE; ENERGY; R404A; CYCLE;
D O I
10.3390/en14186003
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This study evaluates the performance of an R744/R404A cascade refrigeration system (CRS) with internal heat exchangers (IHE) in supermarkets. R744 is used as the refrigerant in a low-temperature cycle, and R404A is used as the refrigerant in a high-temperature cycle. In previous studies, there are many studies including theoretical performance analysis of the CRS. However, experimental studies on the CRS are lacking, and experimental research on the R744/R404A system with an IHE is scarce. Therefore, this study provides basic data for optimal refrigeration system design by experimentally evaluating the results of modifying various parameters. The operating parameters considered in this study include subcooling and superheating, condensing and evaporating temperature, cascade evaporation temperature, and IHE efficiency in the R744 low- and R404A high-temperature cycle. The main results are summarized as follows: (1) By applying the results of this study, energy efficiency is achieved by optimizing the overall coefficient of performance (COP) of the CRS, and the refrigerant charge of the R404A cycle is minimized and economic efficiency is also obtained, enabling operation and maintenance as an environment-friendly system. (2) When designing the CRS, finding the cascade evaporation temperature that has the optimum and maximum COP according to the refrigerant combination should be considered with the highest priority.
引用
收藏
页数:20
相关论文
共 38 条
[21]   Advanced exergetic evaluation of refrigeration machines using different working fluids [J].
Morosuk, T. ;
Tsatsaronis, G. .
ENERGY, 2009, 34 (12) :2248-2258
[22]   Exergoeconomic and environmental analyses of CO2/NH3 cascade refrigeration systems equipped with different types of flash tank intercoolers [J].
Mosaffa, A. H. ;
Farshi, L. Garousi ;
Ferreira, C. A. Infante ;
Rosen, M. A. .
ENERGY CONVERSION AND MANAGEMENT, 2016, 117 :442-453
[23]  
Neksa P., CO2 REFRIGERANT SYST
[24]   Experimental assessment of the retrofit of an internal heat exchanger in refrigeration systems: The effect on energy performance and system operation [J].
Oruc, Vedat ;
Devecioglu, Atilla G. .
APPLIED THERMAL ENGINEERING, 2020, 180
[25]  
Parekh A.D., 2014, INT J MECH MECHATRON, V8, P1351
[26]  
Parmar G.G., 2015, Int. J. Innov. Res. Sci. Eng. Technol, V4, P1839
[27]  
Queiroz M.V.A., 2016, P INT REFR AIR COND, P1
[28]  
Sawalha S, 2005, ASHRAE J, V47, P26
[29]  
Shakya A., 2019, INT J SCI DEV RES, V4-2, P319
[30]  
Son ChangHyo, 2019, [Journal of Power System Engineering, 동력시스템공학회지], V23, P5, DOI 10.9726/kspse.2019.23.2.005