Performance analysis of proposed hybrid air conditioning and humidification-dehumidification systems for energy saving and water production in hot and dry climatic regions

被引:82
作者
Nada, S. A. [1 ]
Elattar, H. F. [1 ]
Fouda, A. [2 ]
机构
[1] Benha Univ, Dept Mech Engn, Benha Fac Engn, Banha 13511, Qalyubia, Egypt
[2] Mansoura Univ, Dept Power Mech Engn, Fac Engn, Mansoura 35516, Egypt
关键词
Water desalination; Air conditioning; Humidification-dehumidification; Energy saving; Energy recovery; DESALINATION SYSTEM; HEAT-PUMP; UNIT;
D O I
10.1016/j.enconman.2015.02.082
中图分类号
O414.1 [热力学];
学科分类号
摘要
Performance of integrative air-conditioning (A/C) and humidification-dehumidification desalination systems proposed for hot and dry climatic regions is theoretically investigated. The proposed systems aim to energy saving and systems utilization in fresh water production. Four systems with evaporative cooler and heat recovery units located at different locations are proposed, analyzed and evaluated at different operating parameters (fresh air ratio, supply air temperature and outside air wet bulb temperature). Other two basic systems are used as reference systems in proposed systems assessment. Fresh water production rate, A/C cooling capacity, A/C electrical power consumption, saving in power consumptions and total cost saving (TCS) parameters are used for systems evaluations and comparisons. The results show that (i) the fresh water production rates of the proposed systems increase with increasing fresh air ratio, supply air temperature and outdoor wet bulb temperature, (ii) powers saving of the proposed systems increase with increasing fresh air ratio and supply air temperature and decreasing of the outdoor air wet bulb temperature, (iii) locating the evaporative cooling after the fresh air mixing remarkably increases water production rate, and (vi) incorporating heat recovery in the air conditioning systems with evaporative cooling may adversely affect both of the water production rate and the total cost saving of the system. Comparison study has been presented to identify systems configurations that have the highest fresh water production rate, highest power saving and highest total cost saving. Numerical correlations for fresh water production rate and total system energy consumption are developed and presented in terms of the controlling parameters. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:208 / 227
页数:20
相关论文
共 37 条
[1]   Water-zeolite adsorption beat pump combined with single effect evaporation desalination process [J].
Al-Ansari, A ;
Ettouney, H ;
El-Dessouky, H .
RENEWABLE ENERGY, 2001, 24 (01) :91-111
[2]   Low temperature humidification dehumidification desalination process [J].
Al-Enezi, G ;
Ettouney, H ;
Fawzy, N .
ENERGY CONVERSION AND MANAGEMENT, 2006, 47 (04) :470-484
[3]   Analysis of single-effect evaporator desalination systems combined with vapor compression heat pumps [J].
Al-Juwayhel, F ;
El-Dessouky, H ;
Ettouney, H .
DESALINATION, 1997, 114 (03) :253-275
[4]  
Aly Narmine H., 2003, DESALINATION, V58, P43
[5]   New proposed system for freeze water desalination using auto reversed R-22 vapor compression heat pump [J].
Attia, Ahmed A. A. .
DESALINATION, 2010, 254 (1-3) :179-184
[6]   Analysis of a mechanical vapor compression desalination system [J].
Aybar, HS .
DESALINATION, 2002, 142 (02) :181-186
[7]   Performance evaluation of a mechanical vapor compression desalination system [J].
Bahar, R ;
Hawlader, MNA ;
Woei, LS .
DESALINATION, 2004, 166 (1-3) :123-127
[8]   Numerical investigation of a simple solar still coupled to a compression heat pump [J].
Ben Halima, Hanen ;
Frikha, Nader ;
Ben Slama, Romdhane .
DESALINATION, 2014, 337 :60-66
[9]   A discussion of "heat pumps as a source of heat energy for desalination of seawater" [J].
Chen, JZ ;
Huang, S .
DESALINATION, 2004, 169 (02) :161-165
[10]  
Ettouney H, 1999, INT J ENERG RES, V23, P431, DOI 10.1002/(SICI)1099-114X(199904)23:5<431::AID-ER491>3.3.CO