Experimental investigations for analyzing performance of a direct evaporative cooling system: A case study

被引:2
作者
Vairagade, Suraj [1 ]
Bopche, Santosh [1 ]
Kanhe, Narendra [2 ]
机构
[1] Bajaj Inst Technol, Dept Mech Engn, Wardha, India
[2] Bajaj Inst Technol, Dept Civil Engn, Wardha, India
关键词
Evaporative cooling; saturation efficiency; temperature; relative humidity; cooling capacity; AIR-CONDITIONING SYSTEM; HOT; ENERGY;
D O I
10.1080/15567036.2022.2089780
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper examines experimentally the performance of direct evaporative cooling system for the hot and dry climate of Vidarbha region (Wardha, Maharashtra, INDIA, 20.75 degrees N, 78.60 degrees E). The evaporative cooling system of larger capacity has been designed for effective cooling of classrooms and laboratory spaces of Bajaj Institute of Technology, an engineering institution located at Wardha District. The cooling structures existing in the literature might not be appropriate for this weather condition. Keeping in view this problem, an evaporative cooling section is fabricated using newly developed porous-cellulose material, structured in the form of a honeycomb, to meet the comfort necessities of hot and dry ambience. The evaporative cooling systems of capacity 6000 CFM have been commissioned in the cooler chambers associated with the amenities described above. Experiments have been conducted in the summer months to examine the saturation efficiency of the system, for various test situations in the amenities. In order to reduce the penetration of sound into the conditioning rooms, the effect of Nitrile rubber sheets was also examined. The direct evaporative cooling system exhibited a saturation efficiency ranging from 45.0% to 68.0% for the different test situations in amenities. The provision of Nitrile rubber inside the walls of cooler chamber could reduce the sound intensity by about 18.8%.
引用
收藏
页码:6078 / 6098
页数:21
相关论文
共 31 条
  • [1] Experimental Investigation of a Direct Evaporative Cooling System for Year-Round Thermal Management with Solar-Assisted Dryer
    Abaranji, Sujatha
    Panchabikesan, Karthik
    Ramalingam, Velraj
    [J]. INTERNATIONAL JOURNAL OF PHOTOENERGY, 2020, 2020
  • [2] Evaluation of the performance of local fibers in evaporative cooling
    Al-Suliman, F
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2002, 43 (16) : 2267 - 2273
  • [3] Alhendal Y., 2018, AM J ENG RES AJER, V7, P277
  • [4] Amer O., 2015, International Journal of Environmental Science and Development, V6, P111, DOI [DOI 10.7763/IJESD.2015.V6.571, 10.7763/IJESD.2015.V6.571]
  • [5] [Anonymous], 2019, ASHRAE Standard 62.2
  • [6] [Anonymous], 2017, IND WEATH DAT
  • [7] [Anonymous], 2019, ISHRAE HVAC HDB
  • [8] Aziz A., 2021, J ADV RES FLUID MECH, V86, P140, DOI [10.37934/arfmts.86.1.140153, DOI 10.37934/ARFMTS.86.1.140153]
  • [9] Numerical modeling of rigid media evaporative cooler
    Beshkani, A
    Hosseini, R
    [J]. APPLIED THERMAL ENGINEERING, 2006, 26 (5-6) : 636 - 643
  • [10] Preparation of natural bio-based Eucommia ulmoides gum/styrene-butadiene rubber composites and the evaluation of their damping and sound absorption properties
    Cao, Renwei
    Deng, Linhui
    Feng, Zhibo
    Zhao, Xiuying
    Li, Xiaolin
    Zhang, Liqun
    [J]. POLYMER, 2021, 213