PMU-based Technique for the Estimation of Line Parameters in Three-phase Electric Distribution Grids

被引:0
|
作者
Puddu, Roberto [1 ]
Brady, Kyle [2 ]
Muscas, Carlo [1 ]
Pegoraro, Paolo Attilio [1 ]
von Meier, Alexandra [2 ]
机构
[1] Univ Cagliari, Dept Elect & Elect Engn, I-09123 Cagliari, Italy
[2] Univ Calif Berkeley, Dept Elect Engn & Comp Sci, Berkeley, CA 94720 USA
关键词
current measurement; impedance measurement; instrument transformers; phasor measurement units; power distribution lines; voltage measurement; STATE ESTIMATION;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Line parameters are the foundation of an electric network model, which is the basis for many monitoring and management applications. Improving the knowledge of these parameters can allow better performance of state estimation and protection measures, among other applications. Phasor Measurement Units (PMUs) can provide synchronized voltage and current measurements, referred to a common time reference (usually the Coordinated Universal Time, UTC). This feature, as well as the high accuracy and reporting rate of PMUs, can be exploited for the evaluation of line parameters of the monitored network. In this paper, a PMU-based algorithm, designed for the estimation of line parameters in a three-phase distribution network, is presented. The estimated parameters include the resistances and reactances in the phase impedance matrix of each three-phase line. The uncertainty induced by the components of the measurement system, mainly instrument transformers and PMUs, is included in the model. The algorithm allows for performing estimations either on a single branch or on a set of branches of the network, using time-aligned and coordinated measurements to improve the estimation accuracy. The validity of the approach is verified though simulations performed on a small portion of a test medium voltage distribution grid.
引用
收藏
页码:1 / 6
页数:6
相关论文
共 50 条
  • [1] Compensation of Systematic Errors for Improved PMU-based Fault Detection and Location in Three-Phase Distribution Grids
    Pegoraro P.A.
    Sitzia C.
    Solinas A.V.
    Sulis S.
    Carta D.
    Benigni A.
    IEEE Transactions on Instrumentation and Measurement, 2024, 73 : 1 - 1
  • [2] PMU-Based Estimation of Systematic Measurement Errors, Line Parameters, and Tap Changer Ratios in Three-Phase Power Systems
    Pegoraro, Paolo Attilio
    Sitzia, Carlo
    Solinas, Antonio Vincenzo
    Sulis, Sara
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2022, 71
  • [3] Practical Experiences on PMU-based Linear State Estimation in Distribution Grids
    Richter, M.
    Wolter, M.
    Naumann, A.
    Komarnicki, P.
    2016 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PESGM), 2016,
  • [4] Model Order Reduction for PMU-Based State Estimation in Distribution Grids
    Carta, Daniele
    Benigni, Andrea
    Muscas, Carlo
    IEEE SYSTEMS JOURNAL, 2018, 12 (03): : 2711 - 2720
  • [5] PMU-Based Detection of Imbalance in Three-Phase Power Systems
    Routtenberg, Tirza
    Xie, Yao
    Willett, Rebecca M.
    Tong, Lang
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (04) : 1966 - 1976
  • [6] Three-phase State Estimation for Distribution Network Based on PMU
    Long, Wu
    Liu, Min
    Wang, Hongliang
    Liu, Rui
    INTERNATIONAL CONFERENCE ON NEW ENERGY AND RENEWABLE RESOURCES (ICNERR 2015), 2015, : 426 - 433
  • [7] PMU-based Line and Transformer Parameter Estimation
    Borda, Carlos
    Olarte, Andres
    Diaz, Hernando
    2009 IEEE/PES POWER SYSTEMS CONFERENCE AND EXPOSITION, VOLS 1-3, 2009, : 1453 - 1460
  • [8] Compensation of Systematic Measurement Errors in a PMU-Based Monitoring System for Electric Distribution Grids
    Pegoraro, Paolo Attilio
    Brady, Kyle
    Castello, Paolo
    Muscas, Carlo
    von Meier, Alexandra
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2019, 68 (10) : 3871 - 3882
  • [9] A PMU-based Technique for the Simultaneous Estimation of Systematic Measurement Errors, Line Parameters and Tap Changer Ratio
    Pegoraro, Paolo Attilio
    Sitzia, Carlo
    Solinas, Antonio Vincenzo
    Sulis, Sara
    2021 IEEE 11TH INTERNATIONAL WORKSHOP ON APPLIED MEASUREMENTS FOR POWER SYSTEMS (AMPS), 2021,
  • [10] PMU-based Distribution System State Estimation
    Bundoc, Paul Eugene Delfin C.
    Orillaza, Jordan Rel C.
    PROCEEDINGS OF TENCON 2018 - 2018 IEEE REGION 10 CONFERENCE, 2018, : 0993 - 0998