Experimental study on transient impedance of grounding rods encased in ground enhancing compounds

被引:25
作者
Androvitsaneas, Vasilios P. [1 ]
Gonos, Ioannis F. [1 ]
Stathopulos, Ioannis A. [1 ]
机构
[1] Natl Tech Univ Athens, High Voltage Lab, Sch Elect & Comp Engn, 9 Iroon Politech St,Zografou Campus, Athens 15780, Greece
关键词
Grounding rods; Ground enhancing compounds; Impulse impedance; Ground resistance; Lightning impulse characteristics; BENTONITE; BEHAVIOR; CURRENTS; SYSTEMS;
D O I
10.1016/j.epsr.2015.11.032
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Aim of this research work is the study on the variation of the impulse impedance and its parameters of grounding rods which are driven in ground enhancing compounds. From the analysis of the measurement results, this work aspires to investigate the possible earned benefits from the usage of these materials on grounding systems, especially in the field of Lightning Protection Systems (LPS). Moreover, the validation of the results of preceding experimental studies on grounding systems transient impedance is another objective of this project. For this purpose, full-scale impulse current tests of a standard waveform have been performed on single vertical grounding rods, driven both into soil and in ground enhancing corn pounds. The injected current into the grounding systems and the developed electric potential on them have been recorded, resulting in the determination of the time variation of impulse impedance. The results provide useful information for the design and the behavior of a grounding system, encased either in bentonite or in conductive concrete under lightning impulse currents, as well as for the protection measures of installations from lightning strokes. (C) 2015 Elsevier B.V. All rights reserved.
引用
收藏
页码:109 / 115
页数:7
相关论文
共 29 条
  • [1] Androvitsaneas V.P., 2014, P 5 INT C HIGH VOLT
  • [2] Androvitsaneas V.P., 2012, P 31 INT C LIGHTN PR
  • [3] Artificial neural network methodology for the estimation of ground enhancing compounds resistance
    Androvitsaneas, Vasilios P.
    Gonos, Ioannis F.
    Stathopulos, Ioannis A.
    [J]. IET SCIENCE MEASUREMENT & TECHNOLOGY, 2014, 8 (06) : 552 - 570
  • [4] Androvitsaneas VP, 2014, 2014 INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), P359, DOI 10.1109/ICLP.2014.6973148
  • [5] [Anonymous], 2013, 802013 ANSIIEEE
  • [6] [Anonymous], 2012, 812012 ANSIIEEE
  • [7] [Anonymous], 2010, Standard IEC 62305-1
  • [8] Galvan A., 2010, P 30 INT C LIGHTN PR
  • [9] Behaviour of grounding systems excited by high impulse currents: the model and its validation
    Geri, A
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (03) : 1008 - 1017
  • [10] Gonos I. F., 1999, Eleventh International Symposium on High Voltage Engineering (Conf. Publ. No.467), P272