Numerical analysis on water treeing deterioration of XLPE cable insulation using combination of FEM and Taguchi method

被引:10
作者
Kim, Chonung [1 ,2 ,3 ]
Duan, Jingkuan [1 ,2 ]
Huang, Xingyi [1 ,2 ]
Kim, Soknam [4 ]
Jiang, Pingkai [1 ,2 ]
Kim, Hyeil [3 ]
Hyon, Sungil [4 ]
机构
[1] Shanghai Jiao Tong Univ, Shanghai Key Lab Elect Insulat & Thermal Aging, Shanghai 200240, Peoples R China
[2] Shanghai Jiao Tong Univ, Dept Polymer Sci & Engn, Shanghai 200240, Peoples R China
[3] Kim Chaek Univ Technol, Dept Elect Engn, Pyongyang, North Korea
[4] Pyongyang 326 Cable & Wire Factory, Pyongyang, North Korea
来源
EUROPEAN TRANSACTIONS ON ELECTRICAL POWER | 2010年 / 20卷 / 06期
关键词
electric field distribution; finite element method; Taguchi method; water treeing; XLPE cable insulation; ELECTRIC-FIELD DISTRIBUTION; POWER-CABLES; MORPHOLOGY; BEHAVIOR;
D O I
10.1002/etep.355
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Water treeing is one of the main deterioration phenomena affecting the service lifetime of the underground crosslinked polyethylene (XLPE) power cables. Factors influencing the water tree growth can be classified in two major groups, namely, the external factors (operational factors) and the internal factors (material factors). The influences of the external factors on the number and the growth rates of water trees have fully understood through the long-term research around the world for the past four decades. However, the effects of the internal factors have been not so much investigated as those of the external ones. Especially, it has been hardly discussed which among the probable internal factors is the most influential to the water treeing phenomena until now. In this paper, the authors have investigated the contributions of individual factors influential to the electric field distribution in the tip of the water tree initiated from the outer surface of XLPE cable insulation considering its thermal degradation, using both the finite element method (FEM) and Taguchi design of experiment methodology (Taguchi method). The numerical and water treeing experiments show that the dielectric properties of the water tree and the XLPE host material are more influential to the enhancement of the electric field intensity in the tree tip than its geometrical parameters, and that the permittivity distribution inside the tree is the most influential factor among all of the internal factors. Copyright (C) 2009 John Wiley & Sons, Ltd.
引用
收藏
页码:747 / 759
页数:13
相关论文
共 28 条
[1]   Water treeing in underground power cables: modelling of the trees and calculation of the electric field perturbation [J].
Acedo, M ;
Radu, I ;
Frutos, F ;
Filippini, JC ;
Notingher, P .
JOURNAL OF ELECTROSTATICS, 2001, 53 (04) :267-294
[2]   Statistical evaluation of water tree lengths in XLPE cables at different temperatures [J].
Al-Arainy, AA ;
Ahaideb, AA ;
Qureshi, MI ;
Malik, NH .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2004, 11 (06) :995-1006
[3]  
BELLET JJD, 1987, IEEE T ELECTR INSUL, V22, P211
[4]   IMPROVING THE QUALITY OF AN OPTIMAL POWER-FLOW SOLUTION BY TAGUCHI METHOD [J].
BOUNOU, M ;
LEFEBVRE, S ;
DO, XD .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1995, 17 (02) :113-118
[5]   THE MORPHOLOGY AND BEHAVIOR OF THE WATER TREE [J].
CHEN, JL ;
FILIPPINI, JC .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1993, 28 (02) :271-286
[6]   Polyethylene crosslinking and water treeing [J].
Ciuprina, F ;
Teissèdre, G ;
Filippini, JC .
POLYMER, 2001, 42 (18) :7841-7846
[7]   When Taguchi meets water treeing [J].
Crine, JP .
IEEE ELECTRICAL INSULATION MAGAZINE, 2000, 16 (03) :13-18
[8]  
DENSLEY RJ, 1990, 1990 IEEE INT S EL I, P3
[9]   Correlation between AC breakdown strength and low frequency dielectric loss of water tree aged XLPE cables [J].
Hvidsten, S ;
Ildstad, E ;
Holmgren, B ;
Werelius, P .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (01) :40-45
[10]   THE INFLUENCE OF STRUCTURE ON WATER TREEING IN CROSSLINKED POLYETHYLENE - TREE MORPHOLOGY AND THE INFLUENCE OF ORGANIC CONTAMINANTS [J].
KARAKELLE, M ;
PHILLIPS, PJ .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1989, 24 (06) :1101-1108