Seismic performance of UHV composite post electrical equipment interconnected using a rigid bus with a sliding fitting

被引:8
作者
He, Chang [1 ]
Zhang, Yue [2 ]
Xie, Qiang [3 ]
Yang, Zhenyu [4 ]
机构
[1] Cent South Univ, Sch Civil Engn, 22 South Shaoshan Rd, Changsha 410075, Peoples R China
[2] State Grid Shanghai Municipal Elect Power Co, Shibei Elect Supply Co, Shanghai, Peoples R China
[3] Tongji Univ, Coll Civil Engn, Shanghai, Peoples R China
[4] Guangzhou Univ, Earthquake Engn Res & Test Ctr, Guangzhou, Peoples R China
基金
中国国家自然科学基金;
关键词
Composite post insulator; shaking table test; adjacent structures; rigid bus; interconnected equipment; RESPONSES; BEHAVIOR;
D O I
10.1177/87552930221077123
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
To evaluate the influence of a rigid bus on the interconnected post electrical equipment with a sliding fitting, this article conducted shaking table tests on two full-scaled +/- 800 kV ultra-high voltage post insulators. Simplifying the rigid bus with a sliding fitting serving as a linear spring and damper allowed us to create a dynamic model of the stand-alone insulators and establish advanced two-piece interconnected post electrical equipment. Later, parametric analyses were carried out on the dynamic model. The results showed that the frequencies of the interconnected system were similar to those of the stand-alone counterparts if the dynamic characteristics of the two interconnected items were similar. The seismic responses of the interconnected system generally decrease compared with those of the stand-alone insulators. Thus, the seismic performance of the rigid bus interconnected electrical equipment system could qualify as having a stand-alone status if the dynamic characteristics of the equipment items are similar. The connection stiffness greatly affects the seismic responses of UHV composite post electrical equipment.
引用
收藏
页码:1705 / 1733
页数:29
相关论文
共 31 条
  • [1] Source parameters for the 1952 Kern County earthquake, California: A joint inversion of leveling and triangulation observations
    Bawden, GW
    [J]. JOURNAL OF GEOPHYSICAL RESEARCH-SOLID EARTH, 2001, 106 (B1) : 771 - 785
  • [2] A method for rapid estimation of dynamic coupling and spectral responses of connected adjacent structures
    Behnamfar, Farhad
    Dorafshan, Sattar
    Taheri, Ali
    Hashemi, Behrokh Hosseini
    [J]. STRUCTURAL DESIGN OF TALL AND SPECIAL BUILDINGS, 2016, 25 (13) : 605 - 625
  • [3] [程永锋 Cheng Yongfeng], 2016, [电网技术, Power System Technology], V40, P3945
  • [4] Clough RW, 1994, DYNAMICS STRUCTURES, V2nd
  • [5] Estimation of displacement at interconnection points of substation equipment subjected to earthquake
    Dastous, JB
    Filiatrault, A
    Pierre, JR
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (02) : 618 - 628
  • [6] Dastous JB, 2010, 201004 PEER
  • [7] Der Kiureghian A, 1999, INTERACTION INTERCON
  • [8] Mechanical behavior of electrical hollow composite post insulators: Experimental and analytical study
    Epackachi, Siamak
    Dolatshahi, Kiarash M.
    Oliveto, Nicholas D.
    Reinhorn, Andrei M.
    [J]. ENGINEERING STRUCTURES, 2015, 93 : 129 - 141
  • [9] Fujisaki E, 2014, EURODYN, P345
  • [10] GUZMAN RA, 1976, J POWER DIV ASCE, V102, P165