A New Current Transducer for On-Line Monitoring of Leakage Current on HV Insulator Strings

被引:12
|
作者
Villalobos, Rodrigo J. [1 ]
Moran, Luis A. [2 ]
Huenupan, Fernando [1 ]
Vallejos, Francisco [1 ]
Moncada, Roberto [1 ]
Pesce, Cristian G. [1 ]
机构
[1] Univ La Frontera, Dept Elect Engn, Temuco 4811230, Chile
[2] Univ Concepcion, Dept Elect Engn, Concepcion 4030000, Chile
关键词
Insulators; Transducers; Leakage currents; Current measurement; Pollution measurement; Transmission line measurements; Pollution; Current transducer; HV insulator strings; leakage current; on-line monitoring; pollution level estimation; CONTAMINATION LEVEL; FLASHOVER PROCESS; CURRENT INDEX; VOLTAGE; POLLUTION; PORCELAIN;
D O I
10.1109/ACCESS.2022.3191349
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Leakage current measurement and its harmonics have been widely used for the pollution level estimation of HV insulator strings. However, the solutions available to applications into transmission lines and substations are few and it reduces the creepage distance (mm/kV), must be installed by de-energizing the electrical power system or do not allow the characteristic harmonics of the leakage current to be obtained. This paper presents the design, implementation, testing, and experimental validation of a transducer for measuring and online monitoring of leakage currents on high-voltage insulator strings. The transducer is composed of a clamp-type current transformer with a supermalloy material core. The leakage current is reconstructed from the transducer output voltage by applying the Fast Fourier Transform (FFT) and its own inverse transfer function, which allows it to obtain the leakage current with its characteristic harmonics and reduces the electromagnetic noise present in power systems. The output voltage of the transducer was acquired, processed, and transmitted using a dedicated device installed in the HV tower. The proposed transducer was first tested on an insulator inside an artificial fog chamber according to the IEC 60507 standard. The transducer was experimentally validated on an insulator string in a 220 kV substation. The results showed that the designed transducer measured the leakage current and its harmonics with an average error less than 1.76%. With these results the transducer can be used for the on-line monitoring of pollution levels of insulator strings without reduces the creepage distance.
引用
收藏
页码:78818 / 78826
页数:9
相关论文
共 50 条
  • [31] Pollution Severity Monitoring of High Voltage Transmission Line Insulators Using Wireless Device Based on Leakage Current Bursts
    Gouda, Osamae
    Darwish, Mohamed M. F.
    Mahmoud, Karar
    Lehtonen, Matti
    Elkhodragy, Tamer M.
    IEEE ACCESS, 2022, 10 : 53713 - 53723
  • [32] Characterization of Leakage Current on the Surface of Porcelain Insulator under Contaminated Conditions
    Terrab, Hocine
    El-Hag, Ayman
    Bayadi, Abdelhafid
    2015 4TH INTERNATIONAL CONFERENCE ON ELECTRIC POWER AND ENERGY CONVERSION SYSTEMS (EPECS), 2015,
  • [33] Leakage Current Analysis of Porcelain Disc Insulator subjected to Unusual Pollutants
    Murthy, Ramakrishna K.
    Rao, Vinayak V.
    Badachi, Chandrashekhar
    Dixit, Pradipkumar
    2016 INTERNATIONAL CONFERENCE ON CIRCUITS, CONTROLS, COMMUNICATIONS AND COMPUTING (I4C), 2016,
  • [34] Leakage Current Response Mechanism of Insulator String String With Ambient Humidity on Days Without Rain
    Wang, Jianguo
    Xi, Yanjun
    Fang, Chunhua
    Cai, Li
    Wang, Jianping
    Fan, Yadong
    IEEE ACCESS, 2019, 7 : 55229 - 55236
  • [35] Frequency Analysis and Recurrent Plot of the Leakage Current to Monitoring the Insulator Surface State
    Maadjoudj, D.
    Mekhaldi, A.
    Teguar, M.
    2018 IEEE 2ND INTERNATIONAL CONFERENCE ON DIELECTRICS (ICD), 2018,
  • [36] Influence of humidity and contamination on the leakage current of 230-kV composite insulator
    Mohammadnabi, S.
    Rahmani, Kh.
    ELECTRIC POWER SYSTEMS RESEARCH, 2021, 194
  • [37] Space charge distribution and leakage current pulses for contaminated glass insulator strings in power transmission lines
    Othman, Nordiana Azlin
    Piah, Mohamed Afendi Mohamed
    Adzis, Zuraimy
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (04) : 876 - 882
  • [38] On-line temperature monitoring in insulation material for HV devices
    Gao, LG
    Jin, LJ
    Wang, ZK
    Lv, CS
    PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2003, : 118 - 121
  • [39] Application of EMD in the de-noise of insulator leakage current
    Zhu Yongli
    Huang Yuanqing
    2009 INTERNATIONAL FORUM ON INFORMATION TECHNOLOGY AND APPLICATIONS, VOL 3, PROCEEDINGS, 2009, : 85 - 88
  • [40] MOA resistive current on-line monitoring and expert diagnosis system
    Wu, Mengmeng
    Xu, Jun
    Yi, Bo
    ADVANCES IN MECHATRONICS AND CONTROL ENGINEERING II, PTS 1-3, 2013, 433-435 : 856 - +