A New Current Transducer for On-Line Monitoring of Leakage Current on HV Insulator Strings

被引:12
|
作者
Villalobos, Rodrigo J. [1 ]
Moran, Luis A. [2 ]
Huenupan, Fernando [1 ]
Vallejos, Francisco [1 ]
Moncada, Roberto [1 ]
Pesce, Cristian G. [1 ]
机构
[1] Univ La Frontera, Dept Elect Engn, Temuco 4811230, Chile
[2] Univ Concepcion, Dept Elect Engn, Concepcion 4030000, Chile
关键词
Insulators; Transducers; Leakage currents; Current measurement; Pollution measurement; Transmission line measurements; Pollution; Current transducer; HV insulator strings; leakage current; on-line monitoring; pollution level estimation; CONTAMINATION LEVEL; FLASHOVER PROCESS; CURRENT INDEX; VOLTAGE; POLLUTION; PORCELAIN;
D O I
10.1109/ACCESS.2022.3191349
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Leakage current measurement and its harmonics have been widely used for the pollution level estimation of HV insulator strings. However, the solutions available to applications into transmission lines and substations are few and it reduces the creepage distance (mm/kV), must be installed by de-energizing the electrical power system or do not allow the characteristic harmonics of the leakage current to be obtained. This paper presents the design, implementation, testing, and experimental validation of a transducer for measuring and online monitoring of leakage currents on high-voltage insulator strings. The transducer is composed of a clamp-type current transformer with a supermalloy material core. The leakage current is reconstructed from the transducer output voltage by applying the Fast Fourier Transform (FFT) and its own inverse transfer function, which allows it to obtain the leakage current with its characteristic harmonics and reduces the electromagnetic noise present in power systems. The output voltage of the transducer was acquired, processed, and transmitted using a dedicated device installed in the HV tower. The proposed transducer was first tested on an insulator inside an artificial fog chamber according to the IEC 60507 standard. The transducer was experimentally validated on an insulator string in a 220 kV substation. The results showed that the designed transducer measured the leakage current and its harmonics with an average error less than 1.76%. With these results the transducer can be used for the on-line monitoring of pollution levels of insulator strings without reduces the creepage distance.
引用
收藏
页码:78818 / 78826
页数:9
相关论文
共 50 条
  • [21] A New On-line Monitoring Method for Stray Current ofDCMetro System
    Peng, Ping
    Zeng, Xiangjun
    Leng, Yang
    Yu, Kun
    Ni, Yanru
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2020, 15 (10) : 1482 - 1492
  • [22] The Experimental Measurements of Surface Leakage Current on the Insulator Model
    Dolnik, Bystrik
    Kolcunova, Iraida
    Briancin, Jaroslav
    Fabian, Martin
    2018 INTERNATIONAL CONFERENCE ON DIAGNOSTICS IN ELECTRICAL ENGINEERING (DIAGNOSTIKA), 2018,
  • [23] Polymeric Insulator Conditions Estimation by Using Leakage Current Characteristics Based on Simulation and Experimental Investigation
    Salem, Ali Ahmed
    Lau, Kwan Yiew
    Abdul-Malek, Zulkurnain
    Mohammed, Nabil
    Al-Shaalan, Abdullah M.
    Al-Shamma'a, Abdullrahman A.
    Farh, Hassan M. H.
    POLYMERS, 2022, 14 (04)
  • [24] Nonintrusive insulator leakage current monitoring system based on fiber optic transmission
    Lv Jianxun
    Guo Xin
    Yuan Haiwen
    Liu Yuanqing
    2015 FIFTH INTERNATIONAL CONFERENCE ON INSTRUMENTATION AND MEASUREMENT, COMPUTER, COMMUNICATION AND CONTROL (IMCCC), 2015, : 885 - 889
  • [25] Risk Assessment of Polluted Glass Insulator Using Leakage Current Index Under Different Operating Conditions
    Salem, Ali Ahmed
    Abd-Rahman, Rahisham
    Al-Gailani, Samir Ahmed
    Salam, Zainal
    Kamarudin, Muhammad Saufi
    Zainuddin, Hidayat
    Yousof, Mohd Fairouz Mohd
    IEEE ACCESS, 2020, 8 : 175827 - 175839
  • [26] Fiber-optic sensor system for leakage current detection on insulator strings of overhead transmission lines
    Oliveira, SC
    Fontana, E
    Cavalcanti, FJMM
    Lima, RB
    Martins, JF
    Meneses-Pacheco, E
    2005 SBMO/IEEE MTT-S INTERNATIONAL MICROWAVE AND OPTOELECTRONICS CONFERENCE (IMOC), 2005, : 466 - 471
  • [27] Leakage current patterns on artificially polluted porcelain and polymer insulator
    Manjang, Salama
    Abduh, Ibrahim
    ICPASM 2005: PROCEEDINGS OF THE 8TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 AND 2, 2006, : 443 - +
  • [28] Study on the measurement of HV insulator's leakage current based on the adaptive noise cancellation theory
    Liu, DC
    Zhang, YW
    Hua, X
    Li, Z
    ASIA-PACIFIC CONFERENCE ON ENVIRONMENTAL ELECTROMAGNETICS, CEEM'2003, PROCEEDINGS, 2003, : 327 - 331
  • [29] Measurement of Leakage Current for Monitoring the Performance of Outdoor Insulators in Polluted Environments
    Ramirez, Isaias
    Hernandez, Ramiro
    Montoya, Gerardo
    IEEE ELECTRICAL INSULATION MAGAZINE, 2012, 28 (04) : 29 - 34
  • [30] Using Chaotic Features of Leakage Current for Monitoring Dynamic Behavior of Surface Discharges on an Ice-Covered Insulator
    Liu, Yong
    Farzaneh, Masoud
    Du, B. X.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (04) : 2607 - 2615