The Characteristics of Electromagnetic Current Transformers with DC Bias

被引:0
作者
Li, Changyun [1 ]
Li, Qingmin [2 ]
Yao, Jinxia [3 ]
Liu, Min [3 ]
机构
[1] Shandong Univ, Sch Elect Engn, Jinan 250061, Shandong, Peoples R China
[2] Shandong Univ, Elect Engn, Shandong, Peoples R China
[3] EPRI Shandong, Elect Engn, Jinan PT-250002, Peoples R China
来源
2009 INTERNATIONAL CONFERENCE ON SUSTAINABLE POWER GENERATION AND SUPPLY, VOLS 1-4 | 2009年
关键词
Current transformers; DC bias; EMTP; Percent error; GEOMAGNETICALLY-INDUCED CURRENTS; POWER-SYSTEM; HYSTERESIS; MODELS;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Both geomagnetically induced currents (GIC) and high voltage direct current (HVDC) projects using the earth as its path can cause direct current flowing in the ground. Direct current flux will be produced and has detrimental effects on power systems. Few references can be found about the effects of dc bias on the current transformer that is very important to both metering and protective aims. In this paper, the characteristics of electromagnetic CTs are discussed. At first, the primary current is determined, and a decaying dc offset is found which will affect the CT's dynamic performance. Then the CT's steady state and transient state characteristics with dc bias are researched. It shows that the turns ratio, direct current and some other parameters have effects on the CT's time-to-saturation which is important to protective engineers. EMTP simulation results confirm the validity of the results.
引用
收藏
页码:73 / +
页数:3
相关论文
共 12 条
  • [1] ALBERTSON VD, 1993, IEEE T POWER DELIVER, V8, P1206
  • [2] A current transformer model based on the Jiles-Atherton theory of ferromagnetic hysteresis
    Annakkage, UD
    McLaren, PG
    Dirks, E
    Jayasinghe, RP
    Parker, AD
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (01) : 57 - 61
  • [3] An improved low-frequency transformer model for use in GIC studies
    Chandrasena, W
    McLaren, PG
    Annakkage, UD
    Jayasinghe, RP
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (02) : 643 - 651
  • [4] ALTERNATIVES FOR BLOCKING DIRECT-CURRENT IN AC SYSTEM NEUTRALS AT THE RADISSON LG2 COMPLEX
    EITZMANN, MA
    WALLING, RA
    HUYNH, H
    GRANGER, M
    SUBLICH, M
    KHAN, A
    THANAWALA, HL
    DUTIL, A
    KAPPENMAN, JG
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (03) : 1328 - 1337
  • [5] Current harmonics measurement by means of current transformers
    Emanuel, Alexander E.
    Orr, John A.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (03) : 1318 - 1325
  • [6] *IEEE, 1996, C371001996 IEEE
  • [7] KAPPENMAN JG, 1981, IEEE T POWER AP SYST, V100, P1078, DOI 10.1109/TPAS.1981.316574
  • [8] DYNAMIC PREISACH MODELS OF HYSTERESIS
    MAYERGOYZ, ID
    [J]. IEEE TRANSACTIONS ON MAGNETICS, 1988, 24 (06) : 2925 - 2927
  • [9] An efficient compensation algorithm for current transformer saturation effects
    Pan, JP
    Vu, K
    Hu, Y
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (04) : 1623 - 1628
  • [10] AN EXPERIMENTAL-ANALYSIS OF DC EXCITATION OF TRANSFORMERS BY GEOMAGNETICALLY INDUCED CURRENTS
    TAKASU, N
    OSHI, T
    MIYAWAKI, F
    SAITO, S
    FUJIWARA, Y
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (02) : 1173 - &