Design Consideration of the Shielding Wire in 10 kV Overhead Distribution Lines Against Lightning-Induced Overvoltage

被引:19
作者
Cao, Jinxin [1 ]
Ding, Yuxuan [1 ]
Du, Yaping [1 ]
Chen, Mingli [1 ]
Qi, Ruihan [2 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hung Hom, Hong Kong, Peoples R China
[2] China Southern Power Grid, Power Res Inst, Guangzhou 510760, Peoples R China
关键词
Wires; Lightning; Voltage control; Grounding; Mathematical model; Resistance; Power distribution lines; overvoltage; overhead distribution line; shielding wire; induced effect; POWER DISTRIBUTION LINES; INDUCED VOLTAGES; PART I; SYSTEMS; EXTENSION; ARRESTERS; STRIKES; FORMULA; MODEL; TOOL;
D O I
10.1109/TPWRD.2020.3031682
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a systematic investigation into the performance of a shielding wire on 10 kV overhead lines (OHLs) against indirect lightning, from the design point of view. The design parameters addressed include the grounding interval, grounding resistance, and position of the shielding wire. As a system outage is usually caused by insulator flashover at OHL poles under indirect lightning, the induced voltages there are investigated with the code developed from the Agrawal model. In the evaluation, the location of a lightning return stroke relative to a grounded or ungrounded pole is considered. It is found that the lightning channel positioned in the front of an ungrounded pole could completely wipe out the effect of the shielding wire. This occurs if the wave from the grounding point arrives later than the time to the peak of the voltage directly arising from the lightning return stroke. It is suggested providing the wire grounding at every pole even if the grounding resistance at some poles is much higher than the design value. Grounding spacing does not affect the induced voltages at the pole generally if the pole has been grounded. One critical parameter is identified, i.e., the distance between the shielding and outer phase wires. Minimizing the distance can effectively reduce the lightning-induced voltages.
引用
收藏
页码:3005 / 3013
页数:9
相关论文
共 47 条
[1]   TRANSIENT-RESPONSE OF MULTI-CONDUCTOR TRANSMISSION-LINES EXCITED BY A NONUNIFORM ELECTROMAGNETIC-FIELD [J].
AGRAWAL, AK ;
PRICE, HJ ;
GURBAXANI, SH .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 1980, 22 (02) :119-129
[2]   An Exact Closed-Form Solution for Lightning-Induced Overvoltages Calculations [J].
Andreotti, A. ;
Assante, D. ;
Mottola, F. ;
Verolino, L. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) :1328-1343
[3]  
Andreotti A., 2013, IEEE T ELECTROMAGN C, V55, P109, DOI [10.1109/TEMC.2012.2205001, DOI 10.1109/TEMC.2012.2205001]
[4]   A New Tool for Calculation of Lightning-Induced Voltages in Power Systems-Part I: Development of Circuit Model [J].
Andreotti, Amedeo ;
Pierno, Antonio ;
Rakov, Vladimir A. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (01) :326-333
[5]   A New Tool for Calculation of Lightning-Induced Voltages in Power Systems-Part II: Validation Study [J].
Andreotti, Amedeo ;
Pierno, Antonio ;
Rakov, Vladimir A. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (01) :334-341
[6]  
[Anonymous], 2006, PROTECTION MV LV NET
[7]  
[Anonymous], 1958, Trans. Roy. Inst. Technol.
[8]   Induced voltage measurements on an experimental distribution line during nearby rocket triggered lightning flashes [J].
Barker, PP ;
Short, TA ;
EybertBerard, AR ;
Berlandis, JP .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (02) :980-995
[9]   Lightning-induced voltages on complex distribution systems: models, advanced software tools and experimental validation [J].
Borghetti, A ;
Gutierrez, JA ;
Nucci, CA ;
Paolone, M ;
Petrache, E ;
Rachidi, F .
JOURNAL OF ELECTROSTATICS, 2004, 60 (2-4) :163-174
[10]  
BRIGHTMAN M., 2017, Introduction: The Anthropology of Sustainability: Beyond development and Progress, P1