Design Consideration of the Shielding Wire in 10 kV Overhead Distribution Lines Against Lightning-Induced Overvoltage

被引:18
|
作者
Cao, Jinxin [1 ]
Ding, Yuxuan [1 ]
Du, Yaping [1 ]
Chen, Mingli [1 ]
Qi, Ruihan [2 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hung Hom, Hong Kong, Peoples R China
[2] China Southern Power Grid, Power Res Inst, Guangzhou 510760, Peoples R China
关键词
Wires; Lightning; Voltage control; Grounding; Mathematical model; Resistance; Power distribution lines; overvoltage; overhead distribution line; shielding wire; induced effect; POWER DISTRIBUTION LINES; INDUCED VOLTAGES; PART I; SYSTEMS; EXTENSION; ARRESTERS; STRIKES; FORMULA; MODEL; TOOL;
D O I
10.1109/TPWRD.2020.3031682
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a systematic investigation into the performance of a shielding wire on 10 kV overhead lines (OHLs) against indirect lightning, from the design point of view. The design parameters addressed include the grounding interval, grounding resistance, and position of the shielding wire. As a system outage is usually caused by insulator flashover at OHL poles under indirect lightning, the induced voltages there are investigated with the code developed from the Agrawal model. In the evaluation, the location of a lightning return stroke relative to a grounded or ungrounded pole is considered. It is found that the lightning channel positioned in the front of an ungrounded pole could completely wipe out the effect of the shielding wire. This occurs if the wave from the grounding point arrives later than the time to the peak of the voltage directly arising from the lightning return stroke. It is suggested providing the wire grounding at every pole even if the grounding resistance at some poles is much higher than the design value. Grounding spacing does not affect the induced voltages at the pole generally if the pole has been grounded. One critical parameter is identified, i.e., the distance between the shielding and outer phase wires. Minimizing the distance can effectively reduce the lightning-induced voltages.
引用
收藏
页码:3005 / 3013
页数:9
相关论文
共 50 条
  • [1] Comprehensive Assessment of Lightning Protection Schemes for 10 kV Overhead Distribution Lines
    Cao, Jinxin
    Du, Yaping
    Ding, Yuxuan
    Qi, Ruihan
    Li, Binghao
    Chen, Mingli
    Li, Zhe
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (03) : 2326 - 2336
  • [2] Observation of Overvoltage at the Terminal of 10 kV Distribution Line by Direct Triggered Lightning
    Wang, Jianguo
    Zhao, Yating
    Fang, Yuquan
    Cai, Li
    Wang, Shoupeng
    Xu, Zhiling
    Cheng, Si
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (05) : 3547 - 3554
  • [3] Lightning-Induced Voltages on Overhead Power Lines with the Use of the Hybrid Method: Influence of the Shielding Wire
    M'Ziou, Nassima
    Mokhnache, Leila
    Boubakeur, Ahmed
    Kattan, Rafic
    PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (03): : 57 - 60
  • [4] Three-Dimensional FDTD Calculation of Lightning-Induced Voltages on a Multiphase Distribution Line With the Lightning Arresters and an Overhead Shielding Wire
    Tatematsu, Akiyoshi
    Noda, Taku
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2014, 56 (01) : 159 - 167
  • [5] Practical Schemes on Lightning Energy Suppression in Arresters for Transformers on 10 kV Overhead Distribution Lines
    Cao, Jinxin
    Du, Yaping
    Ding, Yuxuan
    Qi, Ruihan
    Li, Binghao
    Chen, Mingli
    Li, Zhe
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (05) : 4272 - 4281
  • [6] Calculation of Lightning-Induced Voltages on Overhead Distribution Lines Including Insulation Breakdown
    De Conti, Alberto
    Perez, Ernesto
    Soto, Edison
    Silveira, Fernando H.
    Visacro, Silverio
    Torres, Horacio
    IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) : 3078 - 3084
  • [7] Effect of Overhead Shielding Wires on the Lightning-Induced Voltages of Multiconductor Lines Above the Lossy Ground
    Zhang, Liang
    Wang, Lei
    Yang, Jin
    Jin, Xiaobing
    Zhang, Jinbo
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2019, 61 (02) : 458 - 466
  • [8] Lightning-Induced Voltage on Overhead Lines
    Evdokunin, G. A.
    Petrov, N. N.
    PROCEEDINGS OF THE 2016 IEEE NORTH WEST RUSSIA SECTION YOUNG RESEARCHERS IN ELECTRICAL AND ELECTRONIC ENGINEERING CONFERENCE (ELCONRUSNW), 2016, : 553 - 556
  • [9] Lightning-Induced Overvoltages on Overhead Medium-Voltage Lines
    Piantini, Alexandre
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [10] Lightning-induced voltages on overhead lines over irregular terrains
    Soto, Edison
    Perez, Ernesto
    ELECTRIC POWER SYSTEMS RESEARCH, 2019, 176