Optimal design of grounding system in transmission line

被引:0
作者
Khodr, H. M. [1 ]
Machado e Moura, A. [2 ]
Miranda, Vladimiro [1 ,2 ]
机构
[1] INESC, Campus FEUP,Rua Dr Roberto Frias 378, P-4200465 Oporto, Portugal
[2] Univ Porto, Fac Engn, P-4100 Porto, Portugal
来源
2007 INTERNATIONAL CONFERENCE ON INTELLIGENT SYSTEMS APPLICATIONS TO POWER SYSTEMS, VOLS 1 AND 2 | 2007年
关键词
transmission lines; grounding; lightning; optimization;
D O I
暂无
中图分类号
TP39 [计算机的应用];
学科分类号
081203 ; 0835 ;
摘要
A novel optimization methodology is proposed for the design of transmission line grounding systems, taking into account technical as well as economical considerations. The problem of designing the grounding systems of transmission fines is stated as a linear-integer programming problem in terms of the construction characteristics and the particular requirements of the tower grounding schemes at the supports of each of the different line sections, in order to minimize the variable investment costs, subject to the maximum allowed line outage rate due to the lightning activity. The mathematical statement of the problem allows solutions in which the transmission tower footing resistance changes along the line, depending on the cost and on the particular characteristics of each tower grounding, assuring however, that the average behavior enforces the desired outage rate due to lightning activity, selecting the complementary electrode scheme required at each tower. The methodology is tested on a real case consisting of a 230 kV transmission line, 85.4 Km long, with 180 towers. The linear programming branch and bound mathematical technique was applied for the solution of the test case. Two different simulation approaches for the calculation of the behavior of the fine subject to lightning phenomena were evaluated without loss of generality: the approach proposed in [1], selected as an initial test due to its simplicity, and the improved version presented in [2]. Results are presented and compared to the design obtained through conventional tower design approaches with important reductions in the investment costs, encouraging the use and further development of the methodology.
引用
收藏
页码:280 / +
页数:3
相关论文
共 17 条
  • [1] Accurate modelling of rod driven tower footing
    Almeida, ME
    deBarros, MTC
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (03) : 1606 - 1609
  • [2] ALMEIDA ME, 1999, C PUBL, V467, P267
  • [3] [Anonymous], 1985, IEEE T POWER AP SYST, V104, P919
  • [4] BAZARAA MS, 1990, LINEAR PROGRAMMING N
  • [5] BEWLEY LV, 1963, TRAVELING WAVES TRAN, P127
  • [6] Rigorous analysis of back-flashover outages caused by direct lightning strokes to overhead power lines
    Chowdhuri, P
    Li, S
    Yan, P
    [J]. IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2002, 149 (01) : 58 - 65
  • [7] MODELING FOR LIGHTNING PERFORMANCE CALCULATIONS
    DARVENIZA, M
    SARGENT, MA
    LIMBOURN, GJ
    CHOY, LA
    CALDWELL, RO
    CURRIE, JR
    HOLCOMBE, BC
    STILLMAN, RH
    FROWD, R
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1979, 98 (06): : 1900 - 1908
  • [8] POWER FREQUENCY PERFORMANCE OF TRANSMISSION-LINE STRUCTURE GROUNDS
    DAWALIBI, F
    BAISHIKI, RS
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (06): : 1295 - 1303
  • [9] DAWALIBI F, 1979, IEEE POWER APPARATUS, V6, P2348
  • [10] BEHAVIOR OF GROUNDING SYSTEMS IN MULTILAYER SOILS - A PARAMETRIC ANALYSIS
    DAWALIBI, FP
    MA, J
    SOUTHEY, RD
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (01) : 334 - 341