共 4 条
Transient Electromagnetic Force Analysis of High Temperature Superconducting Fault Current Limiter
被引:0
作者:
Fang, Xu
[1
]
Qiu, Jie
[1
]
Wang, Shuhong
[1
]
Xiao, Hongli
[1
]
Zhang, Jingyin
[2
]
Gong, Weizhi
[2
]
Xin, Ying
[2
]
机构:
[1] Xi An Jiao Tong Univ, Fac Elect Engn, Xian 710049, Shaanxi, Peoples R China
[2] Innopower Superconductor Cable Co Ltd, Beijing 100176, Peoples R China
来源:
APPLIED ELECTROMAGNETICS AND MECHANICS (II)
|
2009年
/
13卷
关键词:
IRON CORE;
TRANSFORMER;
D O I:
暂无
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
In this paper, the transient short current of three-phase saturated core high temperature superconducting (HTS) fault current limiter (FCL) is investigated by using a method combining 3-Dimensional (3D) finite element analysis (FEA) and equivalent dynamic nonlinear model. The numerical computations are verified by the experiment results on a prototype with rated voltage 380V. Based on the short current of three-phase saturated core HTS FCL with rated voltage 220kV, the three-phase transient magnetic field is simulated and analyzed by 3D FEA. According to the simulated results, the transient short-circuit electromagnetic forces distribution is calculated.