A Fault Location Method for HVDC Transmission Lines

被引:3
|
作者
Xing, Luhua [1 ]
Chen, Qing [1 ]
Xue, Binglei [2 ]
机构
[1] Shandong Univ, Minist Educ, Key Lab Power Syst Intelligent Dispatch & Control, Jinan 250100, Peoples R China
[2] Econ &Technol Res Inst State Grid Shandong Elect, Jinan 250100, Peoples R China
来源
MECHATRONICS ENGINEERING, COMPUTING AND INFORMATION TECHNOLOGY | 2014年 / 556-562卷
关键词
distribution current; fault location; fault traveling wave; HVDC transmission; wavelet transform;
D O I
10.4028/www.scientific.net/AMM.556-562.2723
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A fault location method for HVDC (High Voltage Direct Current) transmission lines is proposed in this paper, using voltages and currents measured at two terminals of dc lines in time domain. Fault traveling waves propagate from the fault point to both terminals along the faulted line. The position that the traveling wave head arrives at some moment after the fault can be used to calculate the fault location. To determine the arrival positions of traveling wave head at each time indirectly, propagation characteristic curves of traveling wave heads at local and the remote terminals are calculated with distribution currents using the stationary wavelet transform. The accuracy of fault location will not be affected by transition resistance and fault position. Simulation results show that the presented fault location method can achieve quick and accurate fault location on the whole line under probable operation modes of a bipolar HVDC transmission system.
引用
收藏
页码:2723 / 2727
页数:5
相关论文
共 50 条
  • [1] A Novel Fault Location Method for HVDC Transmission Lines
    Yang, Liming
    Chen, Fufeng
    Xue, Mingjun
    Li, Yuping
    Chen, Shi
    Zou, Lei
    2019 IEEE PES GTD GRAND INTERNATIONAL CONFERENCE AND EXPOSITION ASIA (GTD ASIA), 2019, : 341 - 346
  • [2] A Novel Fault-Location Method for HVDC Transmission Lines
    Suonan, Jiale
    Gao, Shuping
    Song, Guobing
    Jiao, Zaibin
    Kang, Xiaoning
    IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (02) : 1203 - 1209
  • [3] Literature Review of Fault Location Research for HVDC Transmission Lines
    Mao, Wang-qing
    Yang, Qi
    Zhang, Shuang
    Gao, Feng
    Song, Yun-ting
    Yang, Ming-yu
    PROCEEDINGS OF THE 2015 INTERNATIONAL POWER, ELECTRONICS AND MATERIALS ENGINEERING CONFERENCE, 2015, 17 : 357 - 360
  • [4] A review of fault location methods in HVDC transmission lines
    Lei Z.
    Hao L.
    Dai J.
    Zhang L.
    Wang X.
    Cui C.
    Qi J.
    Tang X.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2022, 50 (11): : 178 - 187
  • [5] A Novel Fault Location Method for HVDC Transmission Lines Based on the Wavefront Characteristics of Line-Model Component of Fault Voltage
    Mu, Dalin
    Lin, Sheng
    Li, Xiaopeng
    He, Zhengyou
    Dong, Xinzhou
    IEEE TRANSACTIONS ON POWER DELIVERY, 2024, 39 (06) : 3407 - 3418
  • [6] Active traveling wave fault location for HVDC transmission lines based on pulse injection method
    Lyu, Xilin
    Tang, Xiaojun
    Zha, Kunpeng
    Guo, Ningming
    Li, Kuanhong
    2021 8TH INTERNATIONAL FORUM ON ELECTRICAL ENGINEERING AND AUTOMATION, IFEEA, 2021, : 651 - 656
  • [7] Wavelet-based EMTR method for fault location of VSC-HVDC transmission lines
    Zhang, Xipeng
    Tai, Nengling
    Zheng, Xiaodong
    Huang, Wentao
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 961 - 966
  • [8] Fault location method based on traveling-wave instantaneous frequency for HVDC transmission lines
    Duan J.
    Liu J.
    Lu H.
    Zhao Z.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2016, 36 (07): : 1842 - 1848
  • [9] Fault Location in VSC-HVDC Transmission Lines Based on WEMTR
    Zhang X.
    Tai N.
    Zheng X.
    Huang W.
    Sun K.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2019, 34 (03): : 589 - 598
  • [10] A fault location method for parallel transmission lines
    Sheng, LB