Review of modern diagnostic techniques for assessing insulation condition in aged transformers

被引:507
作者
Saha, TK [1 ]
机构
[1] Univ Queensland, Sch Informat Technol & Elect Engn, Brisbane, Qld 4072, Australia
关键词
insulation condition; transformer diagnostics; transformer ageing; dissolved gas analysis; furan analysis; degree of polymerization; oil insulation; cellulose paper; return voltage; polarisation current; depolarisation current; online monitoring; condition based monitoring;
D O I
10.1109/TDEI.2003.1237337
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Cellulosic paper and oil insulation in a transformer degrade at higher operating temperatures. Degradation is accelerated in the presence of oxygen and moisture. Power transformers being expensive items need to be carefully monitored throughout its operation. Well established time-based maintenance and conservative replacement planning is not feasible in a current market driven electricity industry. Condition based maintenance and online monitoring are now gaining importance. Currently there are varieties of chemical and electrical diagnostic techniques available for insulation condition monitoring of power transformers. This paper presents a description of commonly used chemical diagnostics techniques along with their interpretation schemes. A number of new chemical techniques are also described in this paper. In recent times a number of electrical diagnostic techniques have gained exceptional importance to the utility professionals. Among these techniques polarisation/depolarisation current measurement, return voltage measurement and frequency domain dielectric spectroscopy at low frequencies are the most widely used. This paper describes analyses and interpretation of these techniques for transformer insulation condition assessment.
引用
收藏
页码:903 / 917
页数:15
相关论文
共 81 条
[1]  
Alff J.-J., 2000, Conference Record of the 2000 IEEE International Symposium on Electrical Insulation (Cat. No.00CH37075), P161, DOI 10.1109/ELINSL.2000.845480
[2]   Measuring and understanding the ageing of kraft insulating paper in power transformers [J].
Ali, M ;
Eley, C ;
Emsley, AM ;
Heywood, R ;
Xaio, X .
IEEE ELECTRICAL INSULATION MAGAZINE, 1996, 12 (03) :28-34
[3]   Spectroscopic studies of the ageing of cellulosic paper [J].
Ali, M ;
Emsley, AM ;
Herman, H ;
Heywood, RJ .
POLYMER, 2001, 42 (07) :2893-2900
[4]  
ALLAN D, 1991, IEEE P 3 INT C PROP, V2, P1116
[5]  
[Anonymous], AIEE T
[6]  
[Anonymous], 1991, C9531991 IEEE, DOI DOI 10.1109/IEEESTD.1992.106979
[7]   A novel solid-state material for furfuraldehyde detection [J].
Blue, R ;
Uttamchandani, D ;
Farish, O .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1997, 4 (03) :341-343
[8]   The determination of FFA concentration in transformer oil by fluorescence measurements [J].
Blue, R ;
Uttamchandani, D ;
Farish, O .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1998, 5 (06) :892-895
[9]  
BOGNAR A, 1991, PROCEEDINGS OF THE 3RD INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 AND 2, P723, DOI 10.1109/ICPADM.1991.172167
[10]  
BOGNAR A, 1990, P 33 INT C LARG HIGH, V2