Computation of breakdown voltage of long rod-plane air gaps in large temperature and humidity range under positive standard switching impulse voltage

被引:12
|
作者
Ge, Xing [1 ,2 ]
Ding, Yujian [2 ]
Yao, Xiuyuan [2 ]
Lv, Fangcheng [1 ]
Yang, Bingxue [1 ,2 ]
机构
[1] North China Elect Power Univ, Beijing 102206, Peoples R China
[2] China Elect Power Res Inst, Beijing 100192, Peoples R China
关键词
Long air gap; Switching impulse; Atmospheric correction method; Support vector regression (SVR); Cuckoo search algorithm (CS); STREAMER DISCHARGE; PREDICTION METHOD; FEATURES; MODEL;
D O I
10.1016/j.epsr.2020.106518
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The 50% breakdown voltage of the air gap is an important basis for the design of the external insulation of the high voltage power systems, and the atmospheric conditions have a large impact on the breakdown voltage of the air gap. The temperature and humidity of the operating environment of the high voltage power systems have a wide range. The breakdown voltages of the gaps obtained in the laboratory are mostly near the standard atmospheric conditions, and there is no good way to calculate the discharge voltage outside the standard atmospheric conditions. This paper established a 50% positive switching impulse breakdown voltage prediction model based on the cuckoo search algorithm optimized support vector regression for the rod-plane air gap. This calculation model is used to predict the selected prediction data. The predicted results are basically consistent with the experimental results, and the effect is better than the atmospheric correction results. Finally, the method was used to calculate the 50% positive impulse breakdown voltage of the rod-plane air gap under the extreme temperature and humidity conditions in Beijing. This method provides a new idea for obtaining the air gap breakdown voltage under different atmospheric conditions.
引用
收藏
页数:7
相关论文
共 50 条
  • [1] Computation of inception voltage and inception time of positive impulse corona in rod-plane gaps
    Abdel-Salam, M.
    Allen, N. L.
    Cotton, I.
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2007, 1 (04) : 179 - 184
  • [2] Impulse breakdown of short rod-plane gaps and the influence of humidity
    Mikropoulos, PN
    Stassinopoulos, CA
    IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 1998, 145 (04) : 141 - 146
  • [3] Switching Impulse Breakdown Characteristics of Large Sphere-plane Air Gaps compared with Rod-plane Air Gap
    Chen, She
    Zeng, Rong
    Zhuang, Chijie
    Yu, Zhanqing
    He, Jinliang
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (03) : 839 - 844
  • [4] Characterizing the Breakdown Behavior of Rod-Plane Air gap Under Impulse Over-Voltage
    Nourirad, G.
    Izadi, M.
    Gomes, C.
    Ab Kadir, M. Z. A.
    2014 IEEE 8TH INTERNATIONAL POWER ENGINEERING AND OPTIMIZATION CONFERENCE (PEOCO), 2014, : 450 - 454
  • [5] Calculations of Breakdown Voltage of Rod-plane Air Gaps in the Presence of Water Streams
    Yuan, Yao
    Jiang, Xingliang
    Rowland, Simon M.
    Xiao, An
    Li, Qi
    Wang, Song
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (03) : 1577 - 1587
  • [6] Intelligent computing of positive switching impulse breakdown voltage of rod-plane air gap based on extremely randomized trees algorithm
    Yang, Bingxue
    Ding, Yujian
    Lu, Zhanhui
    Yao, Xiuyuan
    Lei, Ting
    Su, Yu
    ELECTRICAL ENGINEERING, 2021, 103 (06) : 3177 - 3187
  • [7] Intelligent computing of positive switching impulse breakdown voltage of rod-plane air gap based on extremely randomized trees algorithm
    Bingxue Yang
    Yujian Ding
    Zhanhui Lu
    Xiuyuan Yao
    Ting Lei
    Yu Su
    Electrical Engineering, 2021, 103 : 3177 - 3187
  • [8] Altitude correction of switching impulse flashover voltage of rod-plane air gap
    Gu, Chen
    Zhang, Wen-Liang
    Fan, Jian-Bin
    Wang, Xi
    Gaodianya Jishu/High Voltage Engineering, 2012, 38 (01): : 140 - 146
  • [9] Positive switching impulse discharge performance and voltage correction of 1 meter rod-plane air gap
    Jiang, Xingliang
    Bai, Yunqing
    Hui, Jianlin
    Zhang, Zhijin
    2006 INTERNATIONAL CONFERENCE ON POWER SYSTEMS TECHNOLOGY: POWERCON, VOLS 1- 6, 2006, : 1591 - +
  • [10] Impulse Breakdown of Short Rod-plane Air Gaps with a Dielectric Covered Rod
    Mavroidis, P. N.
    Mikropoulos, P. N.
    Stassinopoulos, C. A.
    Rafailidis, P.
    Smaragdakis, G.
    2008 PROCEEDINGS OF THE 43RD INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE, VOLS 1-3, 2008, : 988 - 992